STANDARDS
AND
CERTIFICATION
The MD300 control panel for fire detection and fire warning in buildings is constructed in accordance
with European standards EN54-2:1997/A1:2006 and EN54-4:1997/A1:2002/A2:2006.
The MD300 control panel is BOSEC certified in combination with the Apollo S65 optical smoke detector
(B-9072-FD-904), the Apollo S65 heat A1R detector (B-9072-FD-905) and the Apollo ORBIS multi sensor
detector (B-9072-FD-906).
3
DESCRIPTION
OF
THE
MD300
CONTROL
PANEL
The MD300 conventional fire detection control panel is a detection system with loop identification.
The purpose of a fire detection and fire warning system is to provide early warning of the occurrence
of a fire by means of automatic smoke and/or heat detectors and to warn the person responsible of a
possible danger by means of manual call points.
The building is divided into different zones for the connection of the automatic fire detectors and the
manual call points to the fire detection control panel.
In the event of a fire alarm or fault message, the name of the detector loop is displayed on the LCD
with Touch screen. This loop name describes the part of the building where the automatic fire
detectors or manual call points of the corresponding loop are installed. The loop names are
programmed into the system at the customer’s request during commissioning.
The MD300 conventional fire detection control panel is a compact detection system, built into a plastic
housing with a transparent door. The housing contains the operator front, the power supply, the
batteries and all electronics for reading detector loops and for controlling the outputs. The MD300
non-modular control panel is equipped with 16 detector loops as standard.
The MD300 control panel is equipped with a serial Input/output bus as standard, to which up to 8
repeater panels and 8 extension relay cards can be connected.
The operator console of the MD300 control panel contains all the visual indications and is equipped
with four capacitive buttons for the functions “SILENCE”, “RESET”, “EVACUATION” and “EVACUATION
DELAYED”.
All other operations, such as querying the status of a detector loop and switching off loops, are carried
out by means of the LCD with a touch screen and a clear menu structure.