www.limotec.be
HG0300E02D
19
4.4
THE
VISUAL
INDICATIONS
-
Red LED « FIRE ALARM »: lights up in case of an alarm message on one or more detector loops.
-
Yellow LED « COMMON FAULT »: lights up in the event of a technical failure (fault in the
detector loop, fault in a siren circuit or power supply failure).
-
Yellow LED « SYSTEM FAILURE »: illuminates in case of an internal technical failure (parameter
fault, communication fault, external processor fault, etc.).
-
Yellow LED « SIRENS OFF SERVICE/FAULT »: flashes as soon as an interruption or short circuit
in the cabling of the warning and/or evacuation sirens is detected and illuminates continuously
when the warning and evacuation sirens are out of service. In case of an error in the cabling of
the warning and/or evacuation sirens, this LED lights up together with the yellow LED
“COMMON FAULT”.
-
Yellow LED « COMMON OFF SERVICE »: lights up continuously when one or more detector
loops are out of service or when the warning and evacuation sirens are out of service.
-
Green LED « IN USE »: lights up as soon as the control panel is switched on.
-
Red LED « ALARM TRANSMITTED »: lights up as soon as the set time delay for the transmission
(evacuation) has elapsed.
-
Yellow LED « TRANSMISSION OFF SERVICE/FAULT »: flashes as soon as an interruption or
short circuit in the cabling to the telephone transmitter is detected and illuminates
continuously when the output to the telephone transmitter is out of service. In case of an error
in the cabling to the telephone transmitter, this LED lights up together with the yellow LED
“COMMON FAULT”.
-
White LED « OPERATION »: lights up when the control panel is placed in operating level 2 (the
function button “OPERATION” on the LCD Touch screen is colored black).