www.limotec.be
HG0300E02D
27
-
The correct entry of the access code is confirmed by:
The white LED “OPERATION”
The white LED “RESET”
The white LED “EVACUATION DELAYED”
The function button “OPERATION” on the LCD Touch screen is coloured black
-
Press the “SILENCE” button
↓
Read the information regarding the location of the alarm message on the LCD
and go on to the spot!
↓
FIRE?
↓
YES: EXECUTE THE EVACUATION PLAN!
↓
Restart the evacuation sirens by pressing the function button “EVACUATION”
(if necessary, place the MD300 control panel in operating level 2)
Press “YES” on the LCD to activate the evacuation sirens
↓
NO
↓
Place the corresponding detector loop “OFF SERVICE”
CAUTION: the disabling of a detector loop may only
be carried out by a qualified person !
↓
RESET THE MD300 CONTROL PANEL (control panel in operating level 2)
↓
Remove the cause of the alarm message or
inform the service company in the event of a technical failure
↓
Put the respective detector loop back into service
↓
END