background image

 

13 

U62 

Buzzer warning 

0~1 

0:Warning off 

1:Warning on 

14 

U91 

On/Off

 

0~1

 

0:Disable 

1:Enable

 

0

 

15 

U99 

Password 

0000~9999 

 

1111 

 

7. Control Function Description 

7.1 Cool Control Instruction 

7.1.1 Cool control 

●  When  the  temperature 

“Set  tempe”U22”,  and  the 

compressor  has  stopped  for 

“U10”, the compressor starts. 

● When the temperature 

“Set temperature”

-”U22”, and the compressor has run for “U11”, 

the compressor stops. 

7.1.2 Compressor delay protection   

● After power supply, the compressor is able to start only after the time (U10) has passed. 

● After the compressor stops, it is able to restart again only after the time (U10) has passed. 

● After the compressor starts, it is able to stop only after the time (U11) has passed. 

 

7.2 Heat Control Instruction

 

7.2.1 Heat control 

● When the temperature 

“Set temperature”

-”U22”, and the heat output has run for “U10”, 

the heat output starts. 

●  When  the  temperature 

“Set  tempe”U22”,  and  the 

heat  output  has  stopped  for 

“U11”, the heat output stops. 

7.2.2 Heat output delay protection   

● After power supply, the heat output is able to start only after the time (U10) has passed. 

● After the heat output stops, it is able to restart again only after the time (U10) has passed. 

● After the heat output starts, it is able to stop only after the time (U11) has passed. 

 
7.3 On/Off line function

 

If U91 is set to 1, the thermostat works in “On/Off line mode”. 

When offline, depress 

for 3 seconds, it will switch to online, and start to regulate temp. 

When online, depress 

for 3 seconds, it will switch to offline, and stop to regulate temp. 

The thermostat has auto restart function. 

If U91 

is set to 0, the thermostat will always regulate the temp. after power supplied.   

 

7.4 Buzzer Function 

Buzzer sounds shortly for every key press. When confirming the parameter setting, it sounds 

longer. 3 short beeps means invalid. When the system comes wrong or external alarm input, 

the buzzer alarm function will be off if U62=0, or the buzzer continuous alarming if U62=1. 

After the system problem solved and disappears, press 

P

  key to stop warning. 

 

Summary of Contents for ZL-6250A

Page 1: ...ion Output delay protection Buzzer alarm output External warning input Max high temperature or min low temperature exceed warning Sensor failure warning 3 Size Specification 1 Front panel dimension 78 34 5mm 2 Drilling template 71 29mm 3 Whole machines dimension 78 34 5 71mm 4 Length of sensor s 3m including the sensor probe 4 Technical Specification Temperature Sensor NTC Setting Range 40 120 Dis...

Page 2: ...ernal warning 7 UnL Restore the default parameters 6 Keypad Operation 6 1 Set Cool heating Temperature Keeping S pressed for 3 seconds to enter temperature setting mode The temperature set indicator is blinking and the digital shows the set temperature Press key or to change the set temperature Keeping or pressed it will be adjusted quickly Press S the set temperature will be saved and leave the s...

Page 3: ...ting 1 U10 Compressor power on delay time 0 100min 3 2 U11 Comp MIN continuous work time 0 100min 3 3 U15 Heat output power on delay time 0 300s 0 4 U16 Heat output continuous work time 0 300s 0 5 U20 Room temperature sensor calibration 9 9 9 9 0 6 U22 Temperature difference 0 1 10 0 The hysteresis of control 1 0 7 U52 Over temperature warning delay time 1 180min 30 8 U53 First over temperature wa...

Page 4: ...eat output has stopped for U11 the heat output stops 7 2 2 Heat output delay protection After power supply the heat output is able to start only after the time U10 has passed After the heat output stops it is able to restart again only after the time U10 has passed After the heat output starts it is able to stop only after the time U11 has passed 7 3 On Off line function If U91 is set to 1 the the...

Page 5: ...mperature Calibration Function When there is tolerance between the measured temperature and real temperature set parameter U20 to calibrate The calibration range is 9 9 When setting the parameter the step is 0 1 for every key press Keep the key pressed the set data will increase decrease continuously and quickly 7 8 Restoring the Default Parameters and Password Keep P and keys pressed for 5 second...

Page 6: ...the contactor breaker and the similar Reduce the length of sensors wiring as possible avoid forming a spiral shape near the power devices Avoid direct contact with the internal electronic components After finish and check the electrical wiring layout before connect them to the device please follow this instruction Pay attention the electrical wiring diagram below wrong connection possibly damages ...