Lilytech ZL-6250A Instruction Manual Download Page 6

 

 

 

 

 

9. Electrical Connection   

Warning 

● Electrical wiring must be manipulated by certified electrician. 

● Wrong power supply may damage the device and system seriously. 

● Try with effort to layout the sensors and switches line apart from inductive load lines and 

power supply lines. The sensors and switches lines are not allowed go with the power supply 

lines  and  inductive  load  lines  in  a  same  pipeline,  and  are  not  allowed  to  pass  near  the 

contactor, breaker and the similar. 

●  Reduce  the  length  of  sensors’  wiring  as  possible,  avoid  forming  a  spiral  shape  near  the 

power devices. 

● Avoid direct contact with the internal electronic components. 

●  After  finish  and  check  the  electrical  wiring  layout,  before  connect  them  to  the  device, 

please  follow  this  instruction:  Pay  attention  the  “electrical  wiring  diagram”  below,  wrong 

connection possibly  damages  the device and  the  system,  and  may  be dangerous  to the user. 

All security and protecting device for the equipments are necessary. They are very important 

to protect the equipments, and the user’s safety. 

 

Electrical wiring diagram:

 

 

Summary of Contents for ZL-6250A

Page 1: ...ion Output delay protection Buzzer alarm output External warning input Max high temperature or min low temperature exceed warning Sensor failure warning 3 Size Specification 1 Front panel dimension 78 34 5mm 2 Drilling template 71 29mm 3 Whole machines dimension 78 34 5 71mm 4 Length of sensor s 3m including the sensor probe 4 Technical Specification Temperature Sensor NTC Setting Range 40 120 Dis...

Page 2: ...ernal warning 7 UnL Restore the default parameters 6 Keypad Operation 6 1 Set Cool heating Temperature Keeping S pressed for 3 seconds to enter temperature setting mode The temperature set indicator is blinking and the digital shows the set temperature Press key or to change the set temperature Keeping or pressed it will be adjusted quickly Press S the set temperature will be saved and leave the s...

Page 3: ...ting 1 U10 Compressor power on delay time 0 100min 3 2 U11 Comp MIN continuous work time 0 100min 3 3 U15 Heat output power on delay time 0 300s 0 4 U16 Heat output continuous work time 0 300s 0 5 U20 Room temperature sensor calibration 9 9 9 9 0 6 U22 Temperature difference 0 1 10 0 The hysteresis of control 1 0 7 U52 Over temperature warning delay time 1 180min 30 8 U53 First over temperature wa...

Page 4: ...eat output has stopped for U11 the heat output stops 7 2 2 Heat output delay protection After power supply the heat output is able to start only after the time U10 has passed After the heat output stops it is able to restart again only after the time U10 has passed After the heat output starts it is able to stop only after the time U11 has passed 7 3 On Off line function If U91 is set to 1 the the...

Page 5: ...mperature Calibration Function When there is tolerance between the measured temperature and real temperature set parameter U20 to calibrate The calibration range is 9 9 When setting the parameter the step is 0 1 for every key press Keep the key pressed the set data will increase decrease continuously and quickly 7 8 Restoring the Default Parameters and Password Keep P and keys pressed for 5 second...

Page 6: ...the contactor breaker and the similar Reduce the length of sensors wiring as possible avoid forming a spiral shape near the power devices Avoid direct contact with the internal electronic components After finish and check the electrical wiring layout before connect them to the device please follow this instruction Pay attention the electrical wiring diagram below wrong connection possibly damages ...

Reviews: