background image

 

to confirm.  If the password is wrong, it will shows 

Err

, and returns to the measuring 

temperature  states  after  the  buzzer  beeping  3  times.  If  the  password  is  right,  the  buzzer 

beeps once and enters into the mode. Digital will display a parameter code. Press 

  or 

  to select the parameter code. Press 

S

  to show its value. Press 

  or 

 

to set the value. Press

S

  to return parameter code display status. 

Exit the Mode 

          Keep depressing 

P

  for 3 seconds, the set parameters will be saved, the mode exits. 

          If do not press any key for 30 seconds, the mode will exit without saving all the set data. 

 

ZL-6250A:

 

No 

Parameter 

code 

Function 

Range 

Note 

Factory 

setting 

U10 

Compressor power on delay time 

0

100min 

 

U11 

Comp. MIN continuous work time 

0

100min 

 

U15 

Heat output power on delay time 

0~300s 

 

U16 

Heat output continuous work time 

0~300s 

 

U20 

Room 

temperature 

sensor 

calibration 

-9.9

+9.9 

 

U22 

Temperature difference 

0.1

+10.0

 

The 

hysteresis 

of control 

1.0 

U52 

Over-temperature  warning  delay 

time 

1

180min 

 

30 

U53 

First 

over-temperature 

warning 

delay time after power supply 

0~180 hour 

0: Disable 

U54 

High-temperature 

warning 

deviation value to Max Temp 

Temperature 

difference~60

;

OFF 

OFF(>60.0

): 

Disable 

OFF 

10 

U55 

Low-temperature 

warning 

deviation value to Min Temp 

Temperature 

difference~60

;

OFF 

OFF(>60.0

): 

Disable 

OFF 

11 

U60 

External input warning mode 

0~4 

0:Warning off 

1:On, Lock 

2:On, Unlock 

3:Off, Lock 

4:Off, Unlock 

12 

U61 

External warning input delay 

0~120min 

 

Summary of Contents for ZL-6250A

Page 1: ...ion Output delay protection Buzzer alarm output External warning input Max high temperature or min low temperature exceed warning Sensor failure warning 3 Size Specification 1 Front panel dimension 78 34 5mm 2 Drilling template 71 29mm 3 Whole machines dimension 78 34 5 71mm 4 Length of sensor s 3m including the sensor probe 4 Technical Specification Temperature Sensor NTC Setting Range 40 120 Dis...

Page 2: ...ernal warning 7 UnL Restore the default parameters 6 Keypad Operation 6 1 Set Cool heating Temperature Keeping S pressed for 3 seconds to enter temperature setting mode The temperature set indicator is blinking and the digital shows the set temperature Press key or to change the set temperature Keeping or pressed it will be adjusted quickly Press S the set temperature will be saved and leave the s...

Page 3: ...ting 1 U10 Compressor power on delay time 0 100min 3 2 U11 Comp MIN continuous work time 0 100min 3 3 U15 Heat output power on delay time 0 300s 0 4 U16 Heat output continuous work time 0 300s 0 5 U20 Room temperature sensor calibration 9 9 9 9 0 6 U22 Temperature difference 0 1 10 0 The hysteresis of control 1 0 7 U52 Over temperature warning delay time 1 180min 30 8 U53 First over temperature wa...

Page 4: ...eat output has stopped for U11 the heat output stops 7 2 2 Heat output delay protection After power supply the heat output is able to start only after the time U10 has passed After the heat output stops it is able to restart again only after the time U10 has passed After the heat output starts it is able to stop only after the time U11 has passed 7 3 On Off line function If U91 is set to 1 the the...

Page 5: ...mperature Calibration Function When there is tolerance between the measured temperature and real temperature set parameter U20 to calibrate The calibration range is 9 9 When setting the parameter the step is 0 1 for every key press Keep the key pressed the set data will increase decrease continuously and quickly 7 8 Restoring the Default Parameters and Password Keep P and keys pressed for 5 second...

Page 6: ...the contactor breaker and the similar Reduce the length of sensors wiring as possible avoid forming a spiral shape near the power devices Avoid direct contact with the internal electronic components After finish and check the electrical wiring layout before connect them to the device please follow this instruction Pay attention the electrical wiring diagram below wrong connection possibly damages ...