SFA-5000 • SFA-10000 Profibus
6.4.1 Byte 10 - Operating parameters
Bit
Function
bit = 0
bit = 1
0
Count up
rewinding
the wire
Count up
pulling wire
out
1
disabled
enabled
2
Reserved
3
disabled
enabled
4, 5
Reserved
6
reduced
16 bytes
(6+10)
extended
63 bytes
(6+57)
7
only pos
pos + vel
Default values are highlighted in bold.
Code sequence
This is intended to set whether the count increases (count up information) when
you rewind the wire or when you pull the wire out.
Setting 0 (bit 0
= 0) causes the position value to increase when
you rewind the wire; on the contrary, setting 1 (bit 0
causes the position value to increase when you pull the wire out.
Default = 1 (min. = 0, max. = 1)
WARNING
, then you are required to set a new
parameter).
Class 2 functionality
This is only available when the encoder Class 2 or the encoder Class 2 (+VEL) are
installed (see the SFA-x-PB-8192 Class 2 or SFA-x-PB-8192 Class 2 (+VEL)
submodules).
Two device classes are defined in the encoder profile, one mandatory class (Class
1) and one class with optional functions (Class 2). This encoder implements
functions of both Class 1 and Class 2 for encoders. For any information on the
available encoder classes see the “6.2 Classes of the Device profile” section on
page 43.
0 = Disabled
= Encoder Class 1 is set.
1 = Enabled
= Encoder Class 2 or Encoder Class 2 (+VEL) is set.
Default = 1 (min. = 0, max. = 1)
MAN SFA_5000_10000_PB E 1.0
Profibus® interface
48 of 72