23
Fuses (slowly blowing) at 400 V (3 phase) in front of main switch:
M
3~
380 - 415 V / 50 Hz
440 - 480 V / 60 Hz
main fuse
power cable
max. P [kW]
I [A]
max. P [kW]
I [A]
[A]
A [mm²]
L max.[m]
63G2
0.7
1.6
0.84
1.6
6
1.5
220
63G4
0.37
1.1
0.44
1.1
6
1.5
220
71G2
1.1
2.4
1.3
2.4
6
1.5
220
71G4
0.75
1.9
0.9
1.9
6
1.5
220
80G2
2.2
4.6
2.6
4.6
10
1.5
130
80K4
1.5
3.4
1.8
3.5
6
1.5
220
Table 4: Fuses at 380-415 V / 50 Hz and 440-480 V / 60 Hz
M
3~
220 - 240 V / 50 Hz
250 - 275 V / 60 Hz
main fuse
power cable
max. P [kW]
I [A]
max. P [kW]
I [A]
[A]
A [mm²]
L max.[m]
63G2
0.7
2.8
0.84
2.8
6
1.5
120
63G4
0.37
1.9
0.44
1.9
6
1.5
120
71G2
1.1
4.1
1.3
4.1
10
1.5
70
71G4
0.75
3.4
0.9
3.3
6
1.5
120
80G2
2.2
8.1
2.6
9.7
20
1.5
30
80K4
1.5
5.9
1.8
6.1
16
1,5
40
Table 5: Fuses at 220-240 V / 50 Hz and 250-275 V / 60 Hz
Check if the mains voltage complies with that specified on the type plate.
Connect mains supply lines and control line in accordance with wiring diagram.
The L1, L2, L3 and PE terminals for the mains connection are located under the cap for gear cover.
The line 3 + PE cable (minimum cross section 1.5 mm
2
) are necessary for the connection.
After connection, press the lifting button. If the load moves downwards, swap L1 and L2 supply wires.
The mains supply must be turned off!
If the control is equipped with an emergency stop according to EN 60204-32:2008 it will be a red
mushroom-shaped button on the pendant.
In accordance with European regulations the main switch has to be installed in addition to the
emergency stop. The main switch has to be switched off and has to be returned off after daily operation.
The use of the emergency stop does not constitute the correct shutting down of the equipment.
The connection terminals for the control cable and the electric trolley are located under the gear cap.
The polarity of the supply network phases must be set for clockwise (right turning) rotation. If they are incorrectly set,
the hoist
will operate in reverse and will lift when the “Down” button on the controller is pressed. Please ask your
electrician to set the power supply correctly. The polarity of the supply network is correct if the hoist will lift the load
upwards when the “Up” - button is pressed.
3.2.2
Operating voltages
The standard power supply of the electric chain hoists is 400 volts, 3 phases, 50 Hz.
The electric chain hoists are suitable for the operation with a voltage range of 380 - 415 volts, 3 phases,
50 Hz.
Different voltages and frequencies are available on request.
They are marked on the motor plate.