1. Remove the operating instructions card from the top of the control (Figure A).
2. Separate the face plate from the back plate by firmly pulling apart (Figure B). Be careful not to
damage face plate contacts pins.
3. Place the back plate of the control in the desired location on the wall and pencil mark the wall in
the center of the wire opening, top screw hole and bottom screw hole (Figure C).
4. Remove the back plate and drill a 3/8 in opening in the wall to allow for the wire opening and
1/8 in hole for the wall anchors for the top and bottom screw holes (Figure C).
5. Pull 3 wire 20 gauge (min.) 100 ft length (max.), through the opening in the wall and the wire
opening of the back plate (Figure C).
6. Connect red, green, and yellow to the wiring terminals located on the back plate (Figure C).
7. Secure a single wire to the
wire retainer located on the
back plate (Figure C).
8. Attach the back plate to the
wall using the 2 supplied
screws and anchors.
9. Attach the face plate to the
back plate (Figure B).
Note: Be careful to correctly
align the face plate to avoid
damaging the face plate
contact pins.
10. Insert the operating
instructions card into the
control (Figure A).
11. Connect the 3 wire 20 gauge
(min.) 100 ft length (max.) to
the terminal block located on
ventilator (Figure D).
Main Control Installation
The
Lifestyle MAX Digital Control 99-DXPL01
or optional
Lifestyle MAX Programmable
Control 99-LS01
may be installed onto a flush mounted electrical switch box or it may be surface
mounted onto a wall. Only one master control should be installed to a ventilation system (the face
plate on this illustration may not be exactly the same as yours).
Pay special attention not to damage the contact pins when removing and detaching the face plate (Figure B).
Attention
Figure C
Wire opening
Drill a 3/8 in hole
for the wire
opening.
Wire Retainer
Wiring Terminals
Bottom screw hole
drill a 1/8 in hole for
the bottom screw
and anchor.
Top screw hole
drill a 1/8 in hole
for the top screw
and anchor.
Figure D
Red #3
Yellow #4
Green #5
Figure A
Operating
Instruction
Card
Figure B
Face
Plate
Face
Plate
Contact
Pins
Back
Plate
Dehumidistat
sensor openings
to room air allow
accurate sensor
readings, located
at top and
bottom of control
16