![Lifasa MASTER control Var Instruction Manual Download Page 70](http://html1.mh-extra.com/html/lifasa/master-control-var/master-control-var_instruction-manual_1907739070.webp)
4�10�1� MODBUS CONTROL FRAME
The
Controller MASTER control VAR FAST
controls the CPC3i boards using the
MODBUS
protocol.
In particular, it sends a frame every 200 ms, using
Function 15
: N bits write.
The message is a "broadcast" message, i.e., it will be read by all boards, in any address.
The format of the frame is as follows:
Address
Function
Direction
of 1st bit
No� of bits
No� of bytes
Bits value
CRC
00
0F
0064
0040
08
DD0
to
DD7
XXXX
Address: 00
, Broadcast, all the CPC3i boards receive all the frames.
Function: 0F
, Write function.
Direction of 1st bit: 0064
, the direction of the 1st bit in the CPC3i board is 0x0064.
No� of bits: 0040
, the frame has 64 bits.
No� of bytes: 08
, grouped into 8 byes.
Bits value:
The meaning of the 8 bytes is detailed in
Table 39
.
CRC:
XXXX, CRC character.
Table 39: Meaning of the 8 bytes, DD0 - DD7�
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
DD0
-
thy3_np2
thy2_np2
thy1_np2
-
thy3_np1
thy2_np1
thy1_np1
DD1
-
thy3_np4
thy2_np4
thy1_np4
-
thy3_np3
thy2_np3
thy1_np3
DD2
-
thy3_np6
thy2_np6
thy1_np6
-
thy3_np5
thy2_np5
thy1_np5
DD3
-
thy3_np8
thy2_np8
thy1_np8
-
thy3_np7
thy2_np7
thy1_np7
DD4
-
thy3_np10 thy2_np10 thy1_np10
-
thy3_np9
thy2_np9
thy1_np9
DD5
-
thy3_np12 thy2_np12 thy1_np12
-
thy3_np11 thy2_np11 thy1_np11
DD6
-
thy3_np14 thy2_np14 thy1_np14
-
thy3_np13 thy2_np13 thy1_np13
DD7
-
thy3_np16 thy2_np16 thy1_np16
-
thy3_np15 thy2_np15 thy1_np15
thyn_npx
means thyristor n of the block or peripheral x (This number of peripheral, x, is the
one programmed in the rotating selector for each board).
Note:
The frame asks for the transmission of data to thyristors in up to 16 different steps,
phase by phase. The
Controller MASTER control VAR FAST
regulator has a maximum of
12 outputs, so it does not use the last 4 steps of the frame.
70
Controller MASTER control VAR FAST
Instruction Manual