5.26.- NO. OF OPERATIONS ALARM
In this point the number of operations of any of the
stages above which the alarm
E17
will be triggered
can be configured.
The alarms must be enabled (
“5.19.- ENABLING
ALARMS”
)
Press the
key to enter editing mode. It is
identified by the
symbol and the blinking of
the digits to be modified.
There are thousands of operations (k), so a value of 100 k will mean 100,000 operations.
The
key increases the digit value.
The
key decreases the digit value.
The
key skips to the previous digit.
The
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Maximum value:
99999 k.
Minimum value:
1 k.
If the value entered is lower than the minimum value or higher than the maximum value,
the backlight of the display flashes and the value entered is replaced with the minimum or
maximum value, or with the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
“5.27.-
SIMULATION SCREEN”
.
101
Instruction Manual
Controller MASTER control VAR FAST