Energy III consumed
Parameters
Active Energy III consumed
(kWh or MWh)
Inductive Reactive Energy III consumed
(kvarLh or MvarLh)
Capacitive Reactive Energy III consumed
(kvarCh or MvarCh)
Apparent Energy III
consumed
(kVAh or MVAh)
Press the
key to switch to the
Main
screen.
Energy III generated
Parameters
Active Energy III generated
(kWh or MWh)
Inductive Reactive Energy III generated
(kvarLh or MvarLh)
Capacitive Reactive Energy III generated
(kvarCh or MvarCh)
Apparent Energy III
generated
(kVAh or MVAh)
Operations
Parameters
No� of operations of stage C1 to C12
Three screens show the number of operations
of the 12 possible stages.
for more than 3 seconds: delete the no.
of operations.
This parameter should be associated with an alarm that is activated when the number of oper-
ations exceeds a pre-determined value (for example, 5000 operations) in order to perform the
maintenance of this stage.
There are thousands of operations, so the value displayed is in thousands of operations (which
is the reason for the k icon).
47
Instruction Manual
Controller MASTER control VAR FAST