5.25.- LEAKAGE CURRENT ALARM
In this point the parameters of the leakage current
alarm can be configured.
Four alarms are linked to the leakage current:
(
E13
,
E14
,
E15
and
E16
).
The alarms must be enabled (
“5.19.- ENABLING
ALARMS”
)
Press the
key to enter editing mode. It is
identified by the
symbol and the blinking of
the digits to be modified.
The parameters to be configured are:
The
alarm value:
when the unit exceeds this value, alarm
E13
is triggered.
Search for the responsible stage:
if this parameter is programmed as
ON
, the
unit performs a process of connecting and disconnecting all the stages in order to find
which ones are responsible for the leakage and, once they have been detected, cancels
them so that they cannot connect again. The unit triggers alarms
E13
and
E15
and the
disabled stages are intermittently displayed on the screen.
If the unit has a
Sim
-type operation configured (see section
“5.8.- PROGRAM”
), the
responsible stage's search process will not be done even if it is enabled to do so.
Enable stages:
in this parameter, the stages that were disabled by this alarm are
enabled again (
YES
option).
The
key increases the digit value and the next option.
The
key decreases the digit value and the previous option.
The
key skips to the previous digit.
The
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Maximum value:
999 mA.
Minimum value:
1 mA.
If the value entered is lower than the minimum value or higher than the maximum value,
the backlight of the display flashes and the value entered is replaced with the minimum or
maximum value, or with the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
“
5.27.-
SIMULATION SCREEN”
.