background image

UPStation GXT 3x1

Chapter 4 - Operating modes

(06/02)

Page 15

4.1.7

 

Powering down the UPS with mains available

1

 

Shutdown all connected load equipment.

2

 

Press the OUTPUT OFF/BYPASS button once until a "beep" is heard. The UPS ON LED will extinguish and
the BYPASS LED will light if the BYPASS voltage is within an acceptable range. The load is now powered
through the BYPASS and there is no UPS protection. The UPS will remain in BYPASS MODE OPERATION
until the user continues with the next step to turn the UPS off.

3

 

Press the OUTPUTOFF/BYPASS button for at least 1 second, twice, within a 4 second time-jnterval. The
BYPASS LED will extinguish and all power to the load will stop. The UPS is in OUTPUT OFF MODE
OPERATION and the AC LINE LED will be on.

4

 

To isolate the UPS, turn off the INPUT, OUTPUT, and BATTERY breakers on the rear of the UPS. For
complete isolation, turn off the mains to the UPS.

4.1.8

 

Alternate quick powering down the UPS

The UPS will skip past BYPASS MODE OPERATION directly to OUTPUT OFF MODE OPERATION even
with mains available.

1

 

Shutdown all connected load equipment.

2

 

Press the OUTPUT OFF/BYPASS button for at least 1 second, twice, within a 4 second time internal. The UPS
ON LED will extinguish and the BYPASS LED will light for a short period then extinguish and all power to the
load will stop. The UPS is in OUTPUT OFF MODE OPERATION and the AC LINE LED will be on.

3

 

To isolate the UPS. turn off the INPUT, OUTPUT, and BATTERY breakers on the rear of the UPS. For
complete isolation turn off the mains to the UPS.

NOTE: 

Pressing the OUTPUT OFF/BYPASS button will always remove the load from UPS power protection.

Pressing the OUTPUT OFF/ BYPASS button for at least 1 second, twice, within a 4 second time interval will
always remove power from the load.

4.1.9

 

Manual operation without mains

The UPS operating time is limited by available battery power without mains. The UPS may be manually turned
off after the loads have been turned off to prevent the batteries from being completely drained. It may also be
desirable to power up the loads for a short time without mains power to support a critical operation.

With mains unavailable, the UPS has two possible modes:

 

BATTERY MODE OPERATION -UPS ON and BATTERY LEDs will be on and the inverter will provide
power to the load using battery power.

 

OUTPUT OFF MODE OPERATION -All LED.s will be off and the load will not have power .

4.1.10

 

Powering up the UPS without mains

1

 

Ensure the load equipment is turned off, and all loads are proper1y connected to the UPS output.

2

 

Verify that the BATTERY, INPUT, AND OUTPUT circuit breakers remain closed.

3

 

Press the UPS ON/ALARM/BATTERY TEST button for at least one second until you hear the audible alarm
emit a "double beep" to signal acceptance of the command. After a short delay, the BATTERY LED should
light. The UPS will then initiate a self-test and approximately 10 seconds after these tests are completed, the UPS
ON and BATTERY LEDs will light indicating that the batteries now power the load.

4

 

Connected loads may now be started. If the mains is not restored before the batteries are fully discharged, the
UPS will automatically turn off all power to the load.

NOTE: 

Closely monitor remaining stored energy using the battery capacity LEDs or communication option. If

an orderly shutdown of the load is required, it must be completed before the batteries are fully discharged.

4.1.11

 

Powering down the UPS without mains

1

 

Shutdown all connected load equipment.

2

 

Press the OUTPUT OFF/BYPASS button once until a "beep" is heard. The UPS will switch from BATTERY
MODE OPERATION to OUTPUT OFF MODE OPERATION. All LEDs will turn off and all power to the load
will stop.

3

 

To isolate the UPS, turn off the INPUT, OUTPUT, and BATTERY breakers on the rear of the UPS. For
complete isolation, turn off the AC supply to the UPS.

CAUTION:

 When the UPS is in OUTPUT OFF MODE OPERATION without MAINS, control panel LEDs and

cooling fans will be off. The UPS is not disabled and output power could be restored at any time. Do not attempt to
service the load or UPS without isolating the UPS.

Summary of Contents for UPSTATION GXT3X1-10000

Page 1: ...Manual Reference number 6390010Q En 06 02 U UP PS ST TA AT TI IO ON N G GX XT T T TM M 3 3x x1 1 6 6 8 8 1 10 0 k kV VA A U Us se er r M Ma an nu ua al l...

Page 2: ...D D DR R R...

Page 3: ...with the procedures contained in this manual you should seek immediate assistance from the Liebert Sales Office from whom the equipment was purchased Alternatively contact the Liebert s Customer Servi...

Page 4: ...UPStation GXT 3x1 USER MANUAL Page iv 06 02...

Page 5: ...interference which the user must correct at his own expense 5 Operate the UPS in an indoor environment only in an ambient temperature range of 0 C to 40 C 32 F to 104 F Install it in a clean environm...

Page 6: ...S Indicates AC Input Indicates AC Output Indicates Caution Note the accompanying instruction Indicates the position of a fuse Requests the user to consult the manual for additional information Indicat...

Page 7: ...ion When fitted 7 2 5 Commissioning the UPS 8 2 5 1 Output Voltage Selector Switches 8 3 CONTROLS AND INDICATORS 11 4 OPERATING MODES 13 4 1 Introduction 13 4 1 1 Normal mode operation UPS mode 13 4 1...

Page 8: ...UPStation GXT 3x1 USER MANUAL Page viii 06 02 7 SPECIFICATIONS 23 7 1 Limited Warranty 24...

Page 9: ...3x1 230X models have an additional output isolation transformer For ease of use the UPStation GXT contains a light emitting diode LED display to indicate either load percentage or battery capacity dep...

Page 10: ...at charge the battery system The battery system charges whenever the UPStation GXT is connected to mains power 1 2 5 Battery The UPStation GXT employs valve regulated non spillable lead acid batteries...

Page 11: ...floor without the stabilisers fitted that it does not tip over Follow the instructions in Chapter 2 Stabilisers Levelling feet IMPORTANT Check the UPS rating plate that the UPS is suitable for operat...

Page 12: ...mend that the input mains supply be protected with an MCB capable of withstanding this initial inrush An MCB specified as being TYPE 4 British standard or CURVE D IEC standard is suitable for this pur...

Page 13: ...1 Safety earth cable Properly grounded earthed equipment provide multiple benefits High quality ground earth connections are required for the equipment ground conductors protective earth and groundin...

Page 14: ...with flexible cables this is optional Note Access to the levelling feet is obstructed by the stabiliser brackets on the GXT 3x1 6000 8000 10000 models Adjust the levelling feet as necessary using a 12...

Page 15: ...lose as possible to the end of the cable that connects to the DB9 connector of the UPS Close the ferrite bead so that the ferrite bead s case snaps closed with the cable routed inside the ferrite bead...

Page 16: ...perating instructions to check functionality of the UPS 3 Set the UPS to NORMAL MODE OPERATION UPS mode Check on the output terminals of the UPS for the correct output voltage for the voltage rating o...

Page 17: ...02 Page 9 Figure 2 3 GXT 3x1 6 8 10 kVA Rear panel controls Intellislot Communications Port TM DB 9 Communications Port Terminal Blocks Output Voltage Selector Switches Output Breaker Breakers Input I...

Page 18: ...Chapter 2 Installation UPStation GXT 3x1 Page 10 06 02 This page is left blank intentionally...

Page 19: ...indicators display approximate battery capacity The UPStation GXT 3x1 is equipped with automatic and remote battery test features The automatic test occurs every 14 days if a manual battery test has n...

Page 20: ...act your dealer or Global Services for a battery replacement OUTPUT OFF BYPASS Button This button controls output power to connected load s and has dual functions OUTPUT OFF and BYPASS CAUTION Pressin...

Page 21: ...lies power through the Rectifier PFC to the inverter to generate power for the connected load During battery mode the AC Input LED will extinguish and the Battery LED will illuminate to warn that a ma...

Page 22: ...the UPS will be operated with mains available The UPS can operate in three possible modes with mains available NORMAL MODE OPERATION UPS ON LED will be on and the inverter will provide power to the lo...

Page 23: ...ave been turned off to prevent the batteries from being completely drained It may also be desirable to power up the loads for a short time without mains power to support a critical operation With main...

Page 24: ...or other local safety codes it is necessary to interrupt at the same time with the same pushbutton all mains input supplies to the UPS The pushbutton that provides the UPS remote shutdown must be of t...

Page 25: ...lity to communicate intelligently with stand alone computers network workstations network servers or UNIX hosts via the DB 9 socket located at the rear of the UPS By purchasing the optional Liebert Si...

Page 26: ...S TxD typical RS 232 levels 3 UPS RxD typical RS 232 levels 4 Remote Shutdown 5 12V battery operation 5 Common 6 Remote Shutdown short to pin 5 any mode 7 Low Battery open emitter 8 Mains Fail open em...

Page 27: ...he operator as described below All On bypass due to output overload beep every half second A On bypass due to over temperature condition beep every 4 seconds B On bypass due to DC bus over voltage bee...

Page 28: ...use is blown indicating internal fault Do not attempt to open or service the UPS Contact your dealer or technical support UPS fails to start when on button is pressed Breaker not closed or has tripped...

Page 29: ...are illuminated UPS inverter fault UPS requires service Contact your dealer or technical support Fault indicators and diagnostic LED A C are illuminated UPS failed the battery test Replace batteries C...

Page 30: ...Chapter 6 Troubleshooting UPStation GXT 3x1 Page 22 06 02 This page is left blank intentionally...

Page 31: ...8 cycles min 201 for 96 msec min with transfer to bypass BYPASS PARAMETERS Default Acceptable Input Voltage for transfer to BYPASS Nominal 15 User selectable Default Acceptable Input Frequency for tr...

Page 32: ...or altered serial numbers or to any losses or damages due to act of God or source external to the product misuse accident abuse neglect negligence unauthorised modification alteration or repair use b...

Reviews: