Chapter 2 - Installation
UPStation GXT 3x1
Page 8
(06/02)
2.5
Commissioning the UPS
2.5.1
Output Voltage Selector Switches
The Output Voltage Selector Switches, located on the rear of the UPS, are designed to allow selecting or changing the
desired output voltage to match the mains. The settings to choose from are 208, 220, 230, and 240 VAC output.
NOTE:
NEVER change the switch settings while UPS is on and powering connected loads.
1.
Adjust the output voltage switch settings to the desired value.
2.
Follow the instructions for Powering up the UPS referenced earlier in this manual. Sequence through the operating
modes, using the front panel pushbuttons, in accordance with operating instructions to check functionality of the
UPS.
3.
Set the UPS to NORMAL MODE OPERATION -UPS mode. Check on the output terminals of the UPS, for the
correct output voltage for the voltage rating of the intended loads.
4.
In NORMAL MODE OPERATION -UPS mode, power up customers load and check that it is within the UPS rating
by observing the front panel LED’s.
5.
In UPS mode, press the UPS ON/ALARM /BATTERY TEST pushbutton to carry out battery test and ensure the
load can be supported.
Note:
Full battery capacity will not be available until a battery recharge cycle has been completed.
The UPS is now ready for service In case of problems refer to the fault finding section or call your local distributor for
advice.
230V Units
208 VAC
220 VAC
230 VAC
240 VAC
áá
- both switches up
áâ
- first switch up, second down
ââ
- both switches down (Factory Default)
âá
- first switch down, second up