background image

Chapter 4 - Operating modes

UPStation GXT 3x1

Page 14

(06/02)

4.1.3

 

Bypass mode operation

During BYPASS operation, mains power provides energy to your load and maintains the batteries in a fully charged
state.
The BYPASS will automatically power the load temporarily during overloads of
the inverter, when diagnostics detect equipment problems, or when the operator
selects BYPASS operation. The four green LED’s indicate an approximate level
of load in 25% increments.  If the BYPASS becomes loaded beyond full rating,
the fifth (amber) LED indicator will illuminate and sound an alarm.
The display template indicates the percentage of load on the output.

CAUTION: 

The BYPASS power path does not protect the connected equipment

from disturbances on the mains supply.

4.1.4

 

Output off mode operation

The UPS output may be disabled even when mains or batteries are available. Output power may be enabled or disabled
using both the front panel controls or communication options. The UPS output may be disabled automatically when the
mains is absent for an extended time and batteries have been discharged. When the UPS is standing by in this mode with
the mains power absent, all panel LEDs and cooling fans will turn off. Output power will be restored automatically upon
restoration of mains.

CAUTION:

 The UPS and loads are not isolated from hazardous voltages in this mode and output power could be

restored at any time. Follow instructions for powering down the UPS and fully isolating the equipment for maintenance.

4.1.5

 

Manual operation with mains available

Under normal circumstances, the UPS will be operated with mains available.
The UPS can operate in three possible modes with mains available:

 

NORMAL MODE OPERATION - UPS ON LED will be on and the inverter will provide power to the load.

 

BYPASS MODE OPERATION - BYPASS LED will be on and the bypass will provide power to the load
directly from the mains.

 

OUTPUT OFF MODE OPERATION - UPS ON and BYPASS LEDs will be off and the load will not have
power. AC LINE LED will be on and batteries will recharge.

4.1.6

 

Starting the UPS with mains available

1

 

Ensure the load equipment is turned off, and all loads are proper1y connected to the UPS output.

2

 

Verify that the mains supplying the UPS is turned on by closing any circuit breaker or switch on the supply side
of the UPS.

3

 

Turn On (Close) the BATTERY circuit breaker.

4

 

Turn ON (Close) the INPUT and OUTPUT circuit breakers. After a start-up sequence, the AC INPUT LED
should be on. If this LED is not on, verify that the mains is turned on to the UPS from any external distribution
panel or isolating switch.

5

 

After about 10 seconds, the UPS will automatically default to BYPASS MODE OPERATION. The BYPASS
LED should be on. The load will now receive power, but is not protected from disturbances in the mains.

6

 

Press the UPS ON/ALARM/BATTERY TEST button for at least one second until you hear the audible alarm
"beep" to signal acceptance of the command. After a delay of about 10 seconds, the BYPASS LED will
extinguish, and the UPS ON LED should light The UPS will then initiate a self-test and battery test When these
tests are complete, the UPS is ready for NORMAL UPS OPERATION.

7

 

Confirm that the UPS ON and AC INPUT LEDs are on and the BATTERY and BYPASS LEDs are off.

8

 

Connected load equipment may now be turned on.

Figure 4-3

 

Bypass Mode Operation at

51-75% loading

Summary of Contents for UPSTATION GXT3X1-10000

Page 1: ...Manual Reference number 6390010Q En 06 02 U UP PS ST TA AT TI IO ON N G GX XT T T TM M 3 3x x1 1 6 6 8 8 1 10 0 k kV VA A U Us se er r M Ma an nu ua al l...

Page 2: ...D D DR R R...

Page 3: ...with the procedures contained in this manual you should seek immediate assistance from the Liebert Sales Office from whom the equipment was purchased Alternatively contact the Liebert s Customer Servi...

Page 4: ...UPStation GXT 3x1 USER MANUAL Page iv 06 02...

Page 5: ...interference which the user must correct at his own expense 5 Operate the UPS in an indoor environment only in an ambient temperature range of 0 C to 40 C 32 F to 104 F Install it in a clean environm...

Page 6: ...S Indicates AC Input Indicates AC Output Indicates Caution Note the accompanying instruction Indicates the position of a fuse Requests the user to consult the manual for additional information Indicat...

Page 7: ...ion When fitted 7 2 5 Commissioning the UPS 8 2 5 1 Output Voltage Selector Switches 8 3 CONTROLS AND INDICATORS 11 4 OPERATING MODES 13 4 1 Introduction 13 4 1 1 Normal mode operation UPS mode 13 4 1...

Page 8: ...UPStation GXT 3x1 USER MANUAL Page viii 06 02 7 SPECIFICATIONS 23 7 1 Limited Warranty 24...

Page 9: ...3x1 230X models have an additional output isolation transformer For ease of use the UPStation GXT contains a light emitting diode LED display to indicate either load percentage or battery capacity dep...

Page 10: ...at charge the battery system The battery system charges whenever the UPStation GXT is connected to mains power 1 2 5 Battery The UPStation GXT employs valve regulated non spillable lead acid batteries...

Page 11: ...floor without the stabilisers fitted that it does not tip over Follow the instructions in Chapter 2 Stabilisers Levelling feet IMPORTANT Check the UPS rating plate that the UPS is suitable for operat...

Page 12: ...mend that the input mains supply be protected with an MCB capable of withstanding this initial inrush An MCB specified as being TYPE 4 British standard or CURVE D IEC standard is suitable for this pur...

Page 13: ...1 Safety earth cable Properly grounded earthed equipment provide multiple benefits High quality ground earth connections are required for the equipment ground conductors protective earth and groundin...

Page 14: ...with flexible cables this is optional Note Access to the levelling feet is obstructed by the stabiliser brackets on the GXT 3x1 6000 8000 10000 models Adjust the levelling feet as necessary using a 12...

Page 15: ...lose as possible to the end of the cable that connects to the DB9 connector of the UPS Close the ferrite bead so that the ferrite bead s case snaps closed with the cable routed inside the ferrite bead...

Page 16: ...perating instructions to check functionality of the UPS 3 Set the UPS to NORMAL MODE OPERATION UPS mode Check on the output terminals of the UPS for the correct output voltage for the voltage rating o...

Page 17: ...02 Page 9 Figure 2 3 GXT 3x1 6 8 10 kVA Rear panel controls Intellislot Communications Port TM DB 9 Communications Port Terminal Blocks Output Voltage Selector Switches Output Breaker Breakers Input I...

Page 18: ...Chapter 2 Installation UPStation GXT 3x1 Page 10 06 02 This page is left blank intentionally...

Page 19: ...indicators display approximate battery capacity The UPStation GXT 3x1 is equipped with automatic and remote battery test features The automatic test occurs every 14 days if a manual battery test has n...

Page 20: ...act your dealer or Global Services for a battery replacement OUTPUT OFF BYPASS Button This button controls output power to connected load s and has dual functions OUTPUT OFF and BYPASS CAUTION Pressin...

Page 21: ...lies power through the Rectifier PFC to the inverter to generate power for the connected load During battery mode the AC Input LED will extinguish and the Battery LED will illuminate to warn that a ma...

Page 22: ...the UPS will be operated with mains available The UPS can operate in three possible modes with mains available NORMAL MODE OPERATION UPS ON LED will be on and the inverter will provide power to the lo...

Page 23: ...ave been turned off to prevent the batteries from being completely drained It may also be desirable to power up the loads for a short time without mains power to support a critical operation With main...

Page 24: ...or other local safety codes it is necessary to interrupt at the same time with the same pushbutton all mains input supplies to the UPS The pushbutton that provides the UPS remote shutdown must be of t...

Page 25: ...lity to communicate intelligently with stand alone computers network workstations network servers or UNIX hosts via the DB 9 socket located at the rear of the UPS By purchasing the optional Liebert Si...

Page 26: ...S TxD typical RS 232 levels 3 UPS RxD typical RS 232 levels 4 Remote Shutdown 5 12V battery operation 5 Common 6 Remote Shutdown short to pin 5 any mode 7 Low Battery open emitter 8 Mains Fail open em...

Page 27: ...he operator as described below All On bypass due to output overload beep every half second A On bypass due to over temperature condition beep every 4 seconds B On bypass due to DC bus over voltage bee...

Page 28: ...use is blown indicating internal fault Do not attempt to open or service the UPS Contact your dealer or technical support UPS fails to start when on button is pressed Breaker not closed or has tripped...

Page 29: ...are illuminated UPS inverter fault UPS requires service Contact your dealer or technical support Fault indicators and diagnostic LED A C are illuminated UPS failed the battery test Replace batteries C...

Page 30: ...Chapter 6 Troubleshooting UPStation GXT 3x1 Page 22 06 02 This page is left blank intentionally...

Page 31: ...8 cycles min 201 for 96 msec min with transfer to bypass BYPASS PARAMETERS Default Acceptable Input Voltage for transfer to BYPASS Nominal 15 User selectable Default Acceptable Input Frequency for tr...

Page 32: ...or altered serial numbers or to any losses or damages due to act of God or source external to the product misuse accident abuse neglect negligence unauthorised modification alteration or repair use b...

Reviews: