60 Chapter 8 Options
Liebert
®
ITA 10kVA UPS User Manual
3. Remove four M3 × 10 screws, which are used to fix the LED display panel on the UPS chassis, take out the LED
display panel and relevant cables from the UPS chassis, as shown in Figure 8-18 (b). Disconnect the three cables
that are connected to the LED display panel to remove the LED display panel.
4. Connect the three cables of the LCD display panel, use four M3 × 10 screws to fix the LCD panel, as shown in
Figure 8-18 (c).
5. Install the plastic panel, as shown in Figure 8-18 (d).
Remove
plastic panel
LED display panel
LCD display panel
M3 × 10 screw (4 pcs)
(a)
Unscrew M3 × 10 screws, and
take out the LED display panel
Install LCD display panel,and
fix it with M3 × 10 screw
Plastic panel
M3 × 10 screw (4 pcs)
(b)
(c)
(d)
Figure 8-18 Installation of LCD display panel
警告
危 险
Note
1. When the display panel assembly is replaced, the UPS chassis cover does not need to be opened.
2. The Rotation method of the LCD display panel is completely the same as that of the LED display panel, please see
2.4.1
Tower Installation
for reference.
8.9 Battery Shared Module Of UF-BSO-0100 ITA UPS
The UF-BSO-0100 ITA UPS battery shared module (battery shared module for short) is only applicable to the parallel
system of the 10kVA long back-up UPS. Through this battery shared module, a battery string with large capacity can
provide power for multiple 10kVA UPSs at the same time.
The appearance of the battery shared module is shown in Figure 8-19. See Table 8-10 for its description.
Operation display panel
Ventilation hole
Figure 8-19 Appearance of the battery shared module