Chapter 8 Options 53
Liebert
®
ITA 10kVA UPS User Manual
8.2.3 Backup Timetable Of Standard Battery Module For Single UPS
When the UPS works in Battery mode, at full load, the backup time of two battery modules (15Ah/192V) in standard
configuration is about five minutes. Adding the number of the battery modules can prolong the backup time. See
Table 8-3 for the backup timetable of different battery modules upon full load.
Table 8-3 Backup timetable of standard battery module for single UPS
Number of the
battery module
Capacity
9000W
7000W
5000W
3000W
2000W
1400W
2
15Ah
5.5m
8m
14m
30m
55m
1h20m
3
22Ah
12m
17m
26m
52m
1h30m
2h25m
4
30Ah
18m
23m
40m
1h15m
1h50m
3h10m
5
36Ah
21m
26m
45m
1h25m
2h14m
3h33m
6
43Ah
24m
33m
52m
1h43m
2h48m
3h49m
7
50Ah
26m
35m
55m
1h50m
2h50m
4h
8
56Ah
35m
50m
1h10m
1h59m
2h55m
4h15m
9
65Ah
42m
55m
1h20m
2h15m
3h25m
4h55m
10
72Ah
50m
1h7m
1h30m
2h35m
3h55m
5h40m
警告
危 险
Note
The data in Table 8-3 is only for your reference, because the battery backup time is affected by the battery parameters, factories
and models, aging degree and other factors.
8.3 POD
The POD is an option for the UPS. It can provide safe and reliable power distribution function for users. The POD
options list is given in Table 8-4.
Table 8-4 POD options list
Model
Name
Dimension (Width × Height × Depth, mm)
UF-POD113U11
1-input 1-output 1 + 1 parallel POD
435 × 130 × 640
UF-POD113U31
3-input 1-output 1 + 1 parallel POD
435 ×130 × 640
UF-POD316U31
3-input 1-output 3 + 1 parallel POD
435 × 260 × 640
UF-POD-0100
Output power distribution unit
435 × 85 × 100
8.3.1 1-Input 1-Output 1 + 1 Parallel POD
The appearance of the 1-input 1-output 1 + 1 parallel POD is shown in Figure 8-4.
Plastic panel
Figure 8-4 Appearance of the 1-input 1-output 1 + 1 parallel POD
Remove the plastic panel to reveal the operation panel of the 1-input 1-output parallel POD, as shown in Figure 8-5.