System and Control Options
35
6.8
Setup System - Setup System Info
The Setup System Info options allow users to:
•
Change Password
—used for access to system setup functions
•
Change Date & Time/Automatic Daylight Saving Time
—used to set the Liqui-tect panel’s
date and time and to enable automatic time change for Daylight Saving Time
•
Restore
Defaults—
returns
the Liqui-tect panel to its factory settings
To change any Setup System Info features:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑↓
to
choose
System and
Control
, then press Enter
↵
(see
6.1 - Login
for help)
.
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑↓
to
choose
Setup System
, then press Enter
↵
.
Select Setup System
• From the Setup System Menu, shown at right, use the arrows
↑↓
to
choose
Setup System Info
and press Enter
↵
.
• Use the following steps to access any of the Setup System Info options.
6.8.1 Change Password
A password is required to access the Liqui-tect panel’s system and
control options, as described in
6.1 - Login
. The password consists of
four characters (see
Table 7
for valid characters). The default pass-
word is AAAA.
Changing the password to “0000” eliminates the login requirement
and prevents the login screen from appearing.
Change the Password
To change the password:
• From the Setup System Info Menu, use the arrows
↑↓
to
choose
Change Password
, then press Enter
↵
.
• To change your password:
• Use the arrows
↑↓
to
choose a character.
• Press Enter
↵
to advance to the next character position.
• When finished, press Enter
↵
again.
Reset Password to the Factory Default (“AAAA”)
To reset the password to the factory default of AAAA:
• Locate DIP switch 1 on the unit’s circuit board (see
1.4 - Controller Board Overview
) and move
switches 2, 7 and 8 to the OFF position (down).
• Move the second switch to the ON position, then to the OFF position.
• Move the seventh switch to the ON position, then to the OFF position.
• Move the eighth switch to the ON position, then to the OFF position.
The password should now be AAAA.
Setup System Menu
SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS
↑↓
=NEXT
↵
=SELECT
SETUP REALARM DELAY
SETUP MAPMODE
> SETUP SYSTEM INFO
Setup System Info Menu
SETUP SYSTEM INFO
> CHANGE PASSWORD
CHANGE DATE & TIME
↑↓
=NEXT
↵
=SELECT
FACTORY DEFAULTS
Change Password
CHANGE PASSWORD
AAAA
↑↓
=SELECT
↵