View Status Options
20
5.1
View Cable Status
The Cable Status screens display the overall status of the cable con-
nected to each of the two zones monitored by the Liqui-tect panel, as
well as the length of the cable being monitored and the amount of cur-
rent present in each cable.
To view the status of the cable:
• From the Main Menu, use the arrows
↑↓
to
choose
View Status
, as
shown at right, and then press Enter
↵
.
• From the View Status Menu, use the arrows
↑↓
to
choose
View
Cable Status
and press Enter
↵
.
5.1.1 Cable Status Screens
Each Cable Status screen displays the zone name (
ZN1
or
ZN2
) and its
label (for example,
ZONE 1
or
ZONE 2
) at the top.
Viewing Additional Screens
There are four Cable Status screens—two for each zone.
• To view additional screens, use the arrows
↑↓
.
• To return to the previous screen, press the ESC key.
• When finished viewing the last screen, press Enter
↵
.
Overall Condition
The first screen for each zone shows:
• the zone name (
ZN1
or
ZN2
) and its label (for example,
ZONE 1
or
ZONE 2
)
• the current overall condition of the cable (for example,
NORMAL
)
The cable conditions tracked by the Liqui-tect panel appear in
Table 5
.
Cable Length & Current Value
The second screen for each zone shows:
• the zone name (
ZN1
or
ZN2
) and its label (for example,
ZONE 1
or
ZONE 2
)
• the length of cable being monitored (for example,
1000FT
)—this value may change dynamically by
up to 0.5% as the panel is continuously calculating the distance of the connected cable
• the current reading (
0UA
, where UA represents µA or microAmps)
Table 5
Overall cable conditions
SOURCE
Cable
CONDITIONS
RECORDED
NORMAL
CABLE BREAK
LEAK DETECTED
(& location, e.g., LEAK @ 99 FT)
CONTAMINATED
(& location, e.g., CONTAM @ 44 FT)
NOT INSTALLED
Main Menu
> VIEW STATUS
SYSTEM AND CONTROL
↑↓
=NEXT
↵
=SELECT
View Status Menu
> VIEW CABLE STATUS
VIEW ALARM HISTORY
VIEW ZONE TREND
↑↓
=NEXT
↵
=SELECT
Overall Condition (ZN1)
STATUS ZN1 ZONE 1
NORMAL
↑↓
=NEXT
Length & Current (ZN1)
STATUS ZN1 ZONE 1
LENGTH:
1000FT
CURRENT: 0UA
↑↓
=NEXT
↵
=DONE
Overall Condition (ZN2)
STATUS ZN2 ZONE 2
NORMAL
↑↓
=NEXT
Length & Current (ZN2)
STATUS ZN2 ZONE 2
LENGTH:
3500FT
CURRENT: 0UA
↑↓
=NEXT
↵
=DONE