MFC-202/P Technical Manual
8
Relay
{
7, 8, 9
}
Configuration
Options
: Refer to the table below.
Description
: Defines the activation condition for programmable relays 7, 8 e 9.
Activation Condition
Occurrence Site
Default State
MODBUS
Value
Synchronism Error
Any MFC-202/P
FC
0
FO
1
Configuration Error
Any MFC-202/P
FC
2
FO
3
Communication Error
Any MFC-202/P
FC
4
FO
5
Position Deviation
Any MFC-202/P
FC
6
FO
7
Normal Operation
Any MFC-202/P
NC
8
NA
9
FC: fail closed
FO: fail open
NC: normally closed
NO: normally open
4.1 MODBUS protocol
Parameter
:
Baud Rate
Options
: 9600, 19200, 38400, 57600, 115200 bps.
Description
: baud rate for the RS485 link.
Parameter
:
Format
Options
: 8N1, 8E1, 8O1, 8N2.
Description
: symbol transmission format, where:
◦
8N1
: 8 data bits, no parity, 1 stop bit.
◦
8E1
: 8 data bits, even parity, 1 stop bit.
◦
8O1
: 8 data bits, odd parity, 1 stop bit.
◦
8N2
: 8 data bits, no parity, 2 stop bits.
Parameter
:
Address
Options
: 1 to 247.
Description
: MODBUS address for the MFC-202/P.