MFC-202/P Technical Manual
12
5.4 Communication error
Communication errors are characterized by serial (RS485) communication failures be-
tween networked MFC-202/P controllers. Each MFC-202/P is responsible for a given
transformer, and they must exchange position information to correctly operate. Possible
causes for communication errors are:
.
More than one MFC-202/P set to the same address.
.
Power failure in more than one MFC-202/P.
.
Connection failure between networked MFC-202/Ps.
.
EMI due to lack of shielding.
.
EMI due to failure to ground the cables’ shielding.
.
One or more defective MFC-202/P.