Licht
http://www.licht-labs.com
Rev. A2 (30–05–12)
MFC-202/P Technical Manual
9
4.2 DNP3 protocol (option)
Parameter
:
Baud Rate
Options
: 9600, 19200, 38400, 57600, 115200 bps.
Description
: baud rate for the RS-485 link.
Parameter
:
Format
Options
: 8N1, 8E1, 8O1, 8N2.
Description
: symbol transmission format, where:
◦
8N1
: 8 data bits, no parity, 1 stop bit.
◦
8E1
: 8 data bits, even parity, 1 stop bit.
◦
8O1
: 8 data bits, odd parity, 1 stop bit.
◦
8N2
: 8 data bits, no parity, 2 stop bits.
Parameter
:
Address
Options
: 0x0000 to 0xFFEF.
Description
: DNP3 outstation address in hexadecimal notation.
Parameter
:
Application Layer Confirmation
Options
: Only when transmitting events or multi-fragment responses, Always.
Description
: Selects when the MFC-202/P outstation should request application layer
confirmations.
Parameter
:
Maximum Inter-Octet Gap
Options
: 2 to 100 ms.
Description
: The DNP3 specification states that frames should not have inter-octet gaps.
In accordance, the MFC-202/P never inserts inter-octet gaps when transmitting data.
However, we allow the option to tolerate gaps in incoming transmissions. Frames featuring
inter-octet gaps larger than the
Maximum Inter-Octet Gap
will be quietly dropped.
Parameter
:
Backoff Delay (Fixed)
Options
: 1 to 100 ms.
Description
: See description for
Backoff Delay (Random)
.
Parameter
:
Backoff Delay (Random)
Options
: 1 to 100 ms.
Description
: The MFC-202/P is designed for multi-drop scenarios where more than
one outstation may transmit over the same line. To handle collision avoidance, a backoff