MFC-202/P Technical Manual
4
Manual Commands
Transformers configured as Master or Individual can be manually commanded by an
operator. This command may be local (issued on the controller’s keyboard) or remote
(with digital dry contact inputs).
If a Follower transformer fails to respond to tap change commands, the MFC-202/P will
ignore subsequent commands and signal the error condition. In this scenario, the oper-
ator must reconfigure the transformer as Individual and manually manage the system’s
parallelism until a solution can be found.