MFC-202/P Technical Manual
7
4 Programmable parameters
The MFC-202/P was developed to provide the user with the greatest possible flexiblity,
such that all supervision and configuration can be executed on-site or remotely through
the existing communication channels.
We define all user-configurable parameters as follows:
Parallelism Mode
Options
:
Master
,
Follower
,
Individual
or
Disabled
Description
: Selects if the channel operates as Master, Follower, Individual or Disabled.
Number of Positions
Options
:
2
to
50
Description
: The on-load tap changer’s number of positions.
Resistance per Position
Opções
:
3
to
20
Ω
Descrição
: Resistance in Ω per tap changer position.
Synchronism Error Timeout
Options
:
10
to
100
s
Description
: Interval defined from the instant when failure to follow was detected to
this error’s indication.
Configuration Error Timeout
Options
:
10
to
100
s
Description
: Interval defined from the instant when a configuration failure was detected
to this error’s indication.
Address
Options
:
0 to 15
Description
: Configures this MFC-202/P’s network address. Each tap changer must
have a unique address. A network of MFC-202/Ps can control up to 16 transformers.
Output Current
(if any)
Options
:
0-1
,
0-5
,
0-10
,
0-20
,
4-20
mA
Description
: Refers to the various configurable current loop scales.
This parameter can be only configured using dry contacts.