E5.
.
You can use this test to check the photocells operativity without exit from the commissioning
procedure.
E6.
PHOTOCELLS TESTING
Note: Do not carry out this test if there is no photocell connection.
Press “
-
“ key twice to skip to the next setting menu
OBSTACLE DETECTION SETTING
Factory setting is , resetting by end user should not be required.
Press “
-
” key till the
display shows “
5
”
Press “
P
” , “
5
” must flash
The door automatically
opens
Break the photocells beam.
If the display shows an “
A
”
then photocells have been
connected properly.
If “
A
” does not appear on the
display you have to check again
the photocells connection.
Then press “
P
” key
to save the setting
Press “
-
” key till the
display shows “
6
”
Press “
P
” , “ ”
appears on the display
Press “
+
” key to scroll the
menu below and use “
-
“ key
to select the desired level.
Factory setting
Obstacle detection sensitivity from low to high according to the arrow direction.
Then press “
P
” key
to save the setting
Setting the obstacle detection sensitivity to high may affect the correct door operating
(
I.e. The door will reverse the movement.
)
WARNING
9