Liberty Pumps LSG200 Series Installation Manual Download Page 5

5647000M

Copyright © Liberty Pumps, Inc. 2021 All rights reserved.

5 | EN

Pump System Components

 Control Panel

Manual LSG/LSGX-Series pumps require a separate, approved 

pump control panel for automatic operation. Operation of these 

models will be according to the control selected. Refer to separate 

manufacturer’s instructions supplied with the unit. Verify the 

electrical specifications for the control panel properly match those 

of the pump.
Mounting, installation, and wiring connections are specific to the 

control panel used. Refer to the manufacturer’s instructions 

supplied with the unit.

IMPORTANT: 

When connecting an LSG/LSGX-Series pump to an 

existing control panel, verify the panel is correctly sized and 

equipped for the pump.
Control panels designed for use with the LSG/LSGX-Series pumps 

available from Liberty Pumps can be found at http://

www.LibertyPumps.com/Portals/0/Files/panel_selection_guide.pdf 

or contact Liberty Pumps.
LSG202M-C and LSGX202M-C models require a panel-mounted 

start circuit consisting of a start capacitor, run capacitor, and start 

relay, which are available separately. Refer to Table 1 for these 

control panel components.

Table 1. Control Panel Components 1-Phase

Required Component and 

Specification

Liberty Pumps P/N

208V 1-phase Start Kit

(contains 3 items listed separately below)

Start Capacitor, 200–240 µF 220 VAC

Run Capacitor, 50 µF 370 VAC

Start Relay, Mars Potential Relay 19551 #551

 Overload Protection

Three-phase LSG/LSGX-Series grinder pumps require overload 

protection in the control panel. The motor control unit shall be 

approved and shall be properly sized or adjusted for the full load 

input power indicated on the pump nameplate. It is important to 

properly adjust or select the motor control overload protection. 

The full load amperes on the nameplate should be used as a 

baseline, but it is important to consider that events such as supply 

voltage variation or large solids passing through the pump can 

temporarily increase current draw. To avoid possible nuisance 

tripping, it may be necessary to adjust overloads to a value slightly 

higher than the full load input power indicated on the pump 

nameplate.

 Thermostat

Single-phase pump models are protected from locked rotor and 

running overloads by a thermal overload (thermostat) integrally 

mounted to the motor and wired to shut down the pump if 

overheating occurs. The thermostat resets automatically after the 

pump has cooled.

 Power and Control Cords

Do not remove cord and strain relief, and do not connect 

conduit to pump.

The power and control cords cannot be spliced; a junction box 

may be used.

IMPORTANT: 

Each cord has a green lead. This is the ground wire 

and must be grounded properly per NEC

®

 and/or local codes.

 Float Switches

Pump ON and OFF cycles are controlled by float switches in the 

wet well (basin). Automatic pumps have a “piggyback” float switch 

attached to the side of the pump, while manual pumps have float 

switches attached to the control panel. Refer to control panel or 

switch instructions for proper electrical connection.

 Float Sequence: Piggyback (Automatic Models) 

1.

As the liquid level in the basin rises, the float tilts, closing the 

switch. This starts the pump.

2.

The pump runs until the liquid level falls below the pump OFF 

level of the float (factory set at 7 in), emptying the basin.

 Float Sequence: Simplex (Manual Models) 

1.

As the liquid level in the basin rises, the pump OFF float tilts, 

closing the switch. This level must be set at a minimum of 

7 in. As the liquid level continues to rise, the pump ON float 

tilts. This switch closes, starting the pump.

2.

The pump runs until the liquid level falls below the pump OFF 

float, emptying the basin.

3.

In the event of a malfunctioning float switch, control relay, or 

pump, the liquid level rises and tilts the HIGH LEVEL ALARM 

float. The alarm system will activate.

 Float Sequence: Duplex (Manual Models) 

1.

As the liquid level in the basin rises, the pump OFF float tilts, 

closing the switch. As the liquid level continues to rise, the 

lead pump ON float tilts. This switch closes, starting the lead 

pump.

2.

The pump runs until the liquid level falls below the pump OFF 

float, emptying the basin.

3.

On the next rise of the liquid level, the other pump will start 

on the lead pump ON signal. The pumps will continue to 

alternate their cycles.

Note: 

The ON/OFF float switch differential should be set as to 

not exceed 12 starts per hour.

4.

If the liquid level rises to the lag pump ON float, the second 

pump will start. Both pumps will run until the liquid falls 

below the pump OFF float, emptying the basin.

5.

In the event of a malfunctioning float switch, control relay, or 

pump, the liquid level rises and tilts the HIGH LEVEL ALARM 

float. The alarm system will activate.

K001316

RISK OF ELECTRIC SHOCK

Summary of Contents for LSG200 Series

Page 1: ...ps at 1 800 543 2550 Retain dated sales receipt for warranty Serial Mfg Date Install Date Installation Manual 5647000M Copyright Liberty Pumps Inc 2021 All rights reserved For pressure sewer applicati...

Page 2: ...by its power cord This will damage the power cord and could expose the electrically live wires inside the power cord The electrical power supply shall be located within the length limitations of the p...

Page 3: ...iates poisonous gas buildup and reduces the risk of explosion and fire from these flammable gases Wear adequate Personal Protective Equipment when working on pumps or piping that have been exposed to...

Page 4: ...e Before Use Protect the power and control cords from the environment Unprotected power and control switch cords can allow water to wick through ends into pump or switch housings causing surroundings...

Page 5: ...stat integrally mounted to the motor and wired to shut down the pump if overheating occurs The thermostat resets automatically after the pump has cooled Power and Control Cords Do not remove cord and...

Page 6: ...ineering drawings will generally specify the levels for Pump ON Pump OFF and HIGH LEVEL ALARM If they are not specified the guidelines in Table 2 should be used to determine float switch locations The...

Page 7: ...pplied with a 6 20P 20A cord plug end If a 1 phase pump will be wired directly into a junction box it is necessary to remove the plug Qualified personnel shall complete the wiring in accordance with t...

Page 8: ...are used refer to the separate instructions supplied with the unit for proper installation and operation making sure all gaskets and components are present Liberty Pumps GR20 Guide Rail System featur...

Page 9: ...k valve operation 4 For multiple pumps check for balanced operating times Uneven times indicate a defective unit float switch or control 5 Inspect the control panel for any presence of moisture in enc...

Page 10: ...to Auto position Float switch unable to move to the pump OFF position due to interference with the side of basin or other obstruction Position the pump or float switch so that it has adequate clearan...

Page 11: ...obstruction Pump is airlocked Turn pump off and let set for several minutes then restart Add baffle to reduce trapped air bubbles Capacitor failure in control panel Check capacitors and replace if nee...

Page 12: ...r transportation There is no other express warranty All implied warranties including those of merchantability and fitness for a particular purpose are limited to three years from the date of purchase...

Reviews: