8 Air Conditioner
Installation of Indoor, Outdoor Unit
3. Piping length and the elevation
Gas
Liquid
Standard
Max.
Standard
Max.
24k Btu/h
5/8"(15.88mm) 3/8"(9.52mm)
7.5
50
5
30
35
30k Btu/h
5/8"(15.88mm) 3/8"(9.52mm)
7.5
50
5
30
35
36k Btu/h
5/8"(15.88mm) 3/8"(9.52mm)
7.5
50
5
30
50
Capacity
Pipe Size
Length A(m)
Elevation B(m)
*Additional
(Diameter:Ø)
refrigerant(g/m)
Oil trap
Gas piping
Liquid piping
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
*15m
* Install trap at each
difference in height
15m
A trap is not necessary when the
outdoor unit is installed in a higher
position than the indoor unit.
CAUTION:
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.