LG Multi V Water V ARWM072CAS5 Engineering Manual Download Page 28

50   |   LOOP CIRCUIT DESIGN 

LOOP CIRCUIT DESIGN   |   51

W

ater Loop Circuit Design

Multi V W

ater 5 575V Source Unit Engineering Manual

© LG Electronics Canada, Inc., North York, ON Canada. All rights reserved. “LG” is a registered trademark of LG Corp.

© LG Electronics Canada, Inc., North York, ON Canada. All rights reserved. “LG” is a registered trademark of LG Corp.

WATER CIRCUIT INSTALLATION

Piping System Specifications

Flow Switch, continued.

• The flow switch must be installed at the horizontal pipe of the water source unit's heat 

water-supply outlet. Verify the direction of the water flow before installation. (Picture 1)

• Remove the jumper wire and connect to the communication terminals (4[A] and 4[B]) of 

the water source unit's control box. (Pictures 2, 3) Open the flow switch cover and check 

the wiring diagrams before connecting the wires. Wiring methods can vary by flow switch 

manufacturer.

• If necessary (and after consulting with an LG representative), use the flow rate detection 

contact to adjust flow rate to within the minimum range. (Picture 4)  

Minimum flow rate range of this product is 50%. Adjust the flow switch to the contact 

point when the flow rate reaches 50%. Minimum flow rate range is 50%. When installing 

the Variable Water Flow Control Kit, set minimum water flow to 40% of nominal flow rate.

• If the unit operates while the flow switch contact point is out of the  

permitted range, it can result in performance deterioration or system failure.

• A normally open type of flow switch must be used.

Figure 17:  Flow Switch Install Steps.

Picture 1

Picture 2

Picture 3

Picture 4

Picture 3

4(N)

5(A)

5(B)

Picture 2

Picture 1

The information contained in this sec-

tion is intended for use by an indus-

try-qualified, experienced, certified 

electrician familiar with the NEC who 

is equipped with the proper tools and 

test instruments.

Failure to carefully read and follow all 

instructions in this manual can  

result in personal injury or death.

All electric work must be performed 

by a licensed electrician and con-

form to local building codes or, in the 

absence of  

local codes, with the NEC, and the 

instructions given in this manual. 

If the power source capacity is inadequate or 

the electric work is not performed properly, 

it may result in fire, electric shock, physical 

injury or death.

Refer to local, state, and federal 

codes, and use power wires of suffi-

cient current capacity and rating.

Wires that are too small may generate heat 

and cause a fire, and physical injury or 

death.

Secure all field wiring connections 

with appropriate wire strain relief.

Improperly securing wires will create undue 

stress on equipment power lugs. Inadequate 

connections may generate heat, cause a 

fire, and physical injury or death.

Ensure the system is connected to a 

dedicated power source that provides 

adequate power.

If the power source capacity is inadequate or 

the electric work is not performed properly, 

it may result in fire, electric shock, physical 

injury or death.

Properly tighten all power connec-

tions. 

Loose wiring may overheat at connection 

points, causing a fire, physical injury or 

death.

Do not change the settings of the 

protection devices.

If the protection devices have been by-

passed or is forced to operate improperly, 

or parts other than those specified by LG 

are used, there is risk of fire, electric shock, 

explosion, and physical injury or death.

WARNING

WATER CIRCUIT INSTALLATION

Pipe Insulation

Water pipe insulation is suggested in the following conditions:
• Where water pipe is subject to freezing.

• Water pipe where water can condense on surface of pipe from ambient room temperatures higher than temperature of water in the pipe. If 

water temperature is maintained at 68°F in winter and 86°F in summer, insulation will not be required.

• On boiler water pipes to save energy losses from heat source.

• On condensate drain lines.

• Where required by local code.

Piping System Specifications

Device Protection Details

Strainer on Water Pipe

To protect the water source unit, a strainer with ≥50 

mesh must be installed on the water source unit inlet 

piping. If not installed, the heat exchanger can be  

damaged by particles in the water supply. 
1.  The water-supply circuitry within the plate-type heat 

exchanger is comprised of many small paths /  

channels.

2.  If a strainer with 50 mesh or more is not included, 

foreign particles can partially block the water flow.

3.  When the system operates in heating, the plate- 

type heat exchanger functions as an evaporator, 

therefore, the temperature of the coolant supply 

drops the temperature of the heat-source water  

supply, which can result in ice forming in the water circuitry.

4.  As heating operation progresses, the channels can be partially frozen, which may damage the plate-type heat exchanger.

5.  If the heat exchanger is damaged, the coolant supply and the heat source water supply will mix, and the system will not function.

Flow Switch 

• It is recommended to install a flow switch on the water pipes that are connected to the WSU. 

• Flow switch must be rated for 208-230V and be a normally open type. Flow switch will perform as the 

first protection device when heated water is not supplied. If the required water level is not present 

after installing the flow switch, the water source unit will display a CH24 error code and will stop 

operating.

• When setting the flow switch, it is recommended to use the default set value of the water source unit 

to satisfy the minimum flow rate. Minimum flow rate range is 50%. When installing the Variable Water 

Flow Control Kit, set minimum water flow to 40% of nominal flow rate.

• Select a flow switch following the pressure specification of the water supply system.

1 inch or 

3/4 inch 

socket

Cover

Micro-switch

Adjustment screw

Vibration plate

Bellows

Pad

• If the set value does not satisfy the minimum flow rate, or if the set value is changed by the user  

arbitrarily, it can result in performance deterioration or system failure.

• If the water source unit operates with a hard water supply, the heat exchanger can be damaged or 

system failure can occur.

• If the water source unit displays a CH24 or CH180 error code, it is possible that the interior of the 

plate-type heat exchanger is partially frozen. If this occurs, resolve the partial freezing issue and then 

operate the water source unit again. Causes of partial freezing may be insufficient heat water flow rate, 

water not supplied, insufficient coolant, foreign particles inside plate-type heat exchanger.

Heat Source

(Water)

Refrigerant

1. Scale and mineral deposits

2. Partially frozen

3. Damage 

(cross contamination)

Figure 15:  Potential Heat Exchanger Damage.

Figure 16:  Flow Switch Schematic.

Summary of Contents for Multi V Water V ARWM072CAS5

Page 1: ...ENGINEERING MANUAL Variable Refrigerant Flow Water Source Outdoor Units 6 0 to 48 0 Tons ...

Page 2: ...serious injury CAUTION This symbol indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury This symbol indicates situations that may result in equipment or property damage accidents only This symbol indicates an action that must not be performed Unit Nomenclature 4 LG Air Conditioner Technical Solution LATS 5 6 Refrigerant Charge Worksheet 7 Water So...

Page 3: ...out and validate LG Multi V Variable Refrigerant Flow VRF Multi F Multi F MAX Single Zone and Energy Recovery Ventilator ERV systems directly into CAD drawings LATS Revit integrates the LG LATS program with Revit software It permits engineers to layout and validate Multi V VRF systems directly into Revit drawings AutoCAD and Revit are both registered marks of Autodesk Inc Features All LG product d...

Page 4: ... check to see if Y Branches will also need to be changed Changes to outdoor unit and indoor unit capacities Capacities changes may impact line length changes Additional refrigerant charge quantity Trim Charge Trim charge will change if piping lengths and diameters change The As Built version must reflect installed piping lengths to ensure correct trim charge All documents submitted by the contract...

Page 5: ...ting Laboratories ETL and bear the ETL label Wiring in these units are in accordance with the National Electrical Code NEC Temperature Ranges Heat Pump Configuration In Heat Pump configuration the system can operate in heating only mode with an entering water temperature EWT of 14 F to 113 F Heat pump units can operate in cooling only mode with an EWT of 23 F to 113 F Heat Recovery Configuration I...

Page 6: ... versions of LG s indoor units and water source units are designated Generation 4 Gen 4 For Gen 4 units to operate with Gen 4 features the air conditioning system must meet the following requirements All indoor units heat recovery units and water source units must be Gen 4 All water source units must have Gen 5 software installed Water source units DIP switch 3 must be set to ON factory default se...

Page 7: ... FVC68D Unit Data Refrigerant Type R410A R410ARefrigerant Factory Charge lbs 9 9 9 9 9 9 9 9 9 9 Refrigerant Control Location EEV Indoor Unit Max Number Indoor Units System2 13 16 20 23 32 Sound Press dB A 3 Cooling Heating 46 48 54 54 58 Net Unit Weight lbs 348 348 348 348 348 Shipping Weight lbs 370 370 370 370 370 Communication Cables5 6 2 x 18 AWG Heat Exchanger Stainless Steel Plate Maximum P...

Page 8: ... all projects to ensure correct line sizing Designer must verify the shop drawing design against the as built design using LATS Contractor must also use LG manufactured Y Branch and Header Kits only Table 3 Multi V Water V 575V Units Combination Unit Model Number 36 0 Ton ARWM432CAS5 40 0 Ton ARWM480CAS5 48 0 ARWM576CAS5 Individual Component Model Numbers ARWM144CAS5 x 3 ARWM144CAS5 x 2 ARWM192CAS...

Page 9: ...1 6 14 5 25 16 0 ARWM192CAS5 1 14 2 17 8 30 20 0 ARWM240CAS5 2 7 6 11 6 14 5 9 5 25 15 24 0 ARWM289CAS5 2 11 6 11 6 14 5 14 5 25 25 28 0 ARWM337CAS5 2 14 2 11 6 17 8 14 5 30 25 36 0 ARWM432CAS5 3 11 6 11 6 11 6 14 5 14 5 14 5 25 25 25 40 0 ARWM480CAS5 3 14 2 11 6 11 6 17 8 14 5 14 5 30 25 25 48 0 ARWM576CAS5 3 14 2 14 2 14 2 17 8 17 8 17 8 30 30 30 Multi V Water V 575V Unit Specifications ELECTRIC...

Page 10: ...G is a registered trademark of LG Corp Single Frame Heat Pump and Heat Recovery DIMENSIONS Dual Frame Heat Pump and Heat Recovery DIMENSIONS Job Name Location ARWM072CAS5 Multi VTM Water 5 Heat Pump Heat Recovery 6 Ton Water Source Unit Tag No Date PO No Job Name Location Tag No Date PO No Page 2 of 2 For continual product development LG reserves the right to change specifications without notice A...

Page 11: ...a Inc North York ON Canada All rights reserved LG is a registered trademark of LG Corp Triple Frame Heat Pump and Heat Recovery DIMENSIONS WIRING DIAGRAMS 6 8 10 12 16 Tons Multi V Water V 575V Job Name Location Tag No Date PO No Page 2 of 2 For continual product development LG reserves the right to change specifications without notice ARWM576CAS5 Multi VTM Water 5 Heat Pump Heat Recovery 48 Ton W...

Page 12: ... Pressure Sensor Strainer Check Valve Service Valve 4 Way Valve Solenoid Valve Temperature Sensor High Pressure Liquid High Pressure Vapor Low Pressure Vapor M M S S Sub Cooling HEX EEV EEV Water Outlet pipe Water Inlet pipe Plate HEX Water Outlet Temp Outside Air Temp REFRIGERANT FLOW DIAGRAMS Multi V Water V Heat Pump Config Heating Operation 575V 6 8 10 12 16 Ton M M S EEV EEV Sub Cooling HEX I...

Page 13: ...ve High Pressure Sensor Water Out Water In Water Outlet Temperature Sensor Sub Cooling HEX REFRIGERANT FLOW DIAGRAMS 575V 6 8 10 12 16 Ton Multi V Water V Heat Recovery Config Heating Operation s s s s s s s s s s s s HR unit HighTemperature High Pressure Liquid HighTemperature High Pressure Vapor LowTemperature Low Pressure Vapor IDU HEX IDU Flare Joint Flare Joint M EEV IDU HEX IDU Flare Joint F...

Page 14: ...nt Flare Joint M EEV IDU HEX IDU Flare Joint Flare Joint M EEV IDU HEX IDU Flare Joint Flare Joint M EEV s Remarks Check Valve EEV Solenoid Valve Pressure Sensor Strainer Temperature Sensor SVC Valve Pressure Switch S C h a r g i n g P o r t REFRIGERANT FLOW DIAGRAMS 575V 6 8 10 12 16 Ton Multi V Water V Heat Recovery Config Heating Based Simultaneous Operation Heating ON Heating ON Heating ON Coo...

Page 15: ... a l v e H i g h P r e s s u r e Se n s o r W a t e r O u t W a t e r I n W a t e r O u t l e t T e m p e r a t u r e Se n s o r H i g h P r e s s u r e V a p o r P i p e L o w P r e s s u r e V a p o r P i p e L i q u i d P i p e C h a r g i n g P o r t REFRIGERANT FLOW DIAGRAMS 575V 6 8 10 12 16 Ton Multi V Water V Heat Recovery Config Oil Return Heating ON Heating ON Heating ON Cooling ON HR un...

Page 16: ...0 ton 59 ARWM432CAS5 36 0 ton 59 ARWM480CAS5 40 0 ton 61 ARWM576CAS5 48 0 ton 63 Measurement taken 3 3 above finished floor and at a distance of 3 3 from face of unit Measurements taken with no attenuation and units operating at full load normal operating condition Sound level will vary depending on a range of factors such as construction acoustic absorption coefficient of particular area in which...

Page 17: ...s Canada Inc North York ON Canada All rights reserved LG is a registered trademark of LG Corp Multi V Water V 575V continued ARWM288CAS5 ARWM336CAS5 ACOUSTIC DATA Sound Pressure Levels ARWM432CAS5 ARWM480CAS5 HEAD LOSS BY WATER FLOW Multi V Water V 575V Systems ARWM576CAS5 Multi V Water V 575V Models ARWM072CAS5 ARWM096CAS5 ARWM 121CAS5 ARWM144CAS5 ARWM192CAS5 0 2 4 6 8 10 12 14 0 10 20 30 40 50 6...

Page 18: ...2 12 7 I D 3 8 9 52 X2 4 5 16 110 I D 1 25 4 I D 3 4 19 05 I D 3 4 19 05 I D 7 8 22 2 I D 1 25 4 I D 1 25 4 I D 7 8 22 2 13 5 8 346 14 15 16 379 3 3 4 96 3 2 3 3 2 I D 7 8 22 2 I D 1 2 12 7 I D 1 4 6 35 4 5 16 110 O D 1 1 8 28 58 I D 7 8 22 2 4 1 2 115 X2 3 15 16 100 O D 5 8 15 88 I D 1 2 12 7 2 3 4 70 O D 7 8 22 2 I D 5 8 15 88 I D 3 4 19 05 4 3 4 120 O D 1 1 2 38 1 I D 1 3 8 34 9 I D 1 1 8 28 58...

Page 19: ...or Dual Frame Systems ACCESSORIES Outdoor Unit Y Branches Outdoor Unit Y branches for Heat Recovery Configuration For Dual Frame Systems For Triple Frame Systems ACCESSORIES Outdoor Unit Y Branches Combination specification Combination specification Low pressure Vapor Pipe Liquid Pipe High pressure Vapor Pipe Multi frame Connector ARCNB21 ARCNB21 ARCNB31 Liquid Pipe Unit inch Unit inch Low pressur...

Page 20: ...15 16 5 15 16 4 3 4 4 3 4 14 3 16 I D 3 8 I D 3 8 I D 1 4 I D 1 4 I D 3 8 I D 1 2 Headers for Heat Pump and Heat Recovery Configuration Headers ACCESSORIES LG headers serve as central connections for multiple runout pipe segments terminating at indoor units Headers must be used with LG systems and be properly installed following the instructions in the applicable LG manual Field supplied headers a...

Page 21: ...ard PCB using an accessory cable without the need for a separate interface device The main screen for LGMV allows the user to view the following real time data on one screen Additional screens can be accessed by tabs on the main screen 1 Cycleview Graphic of internal components including 2 Graph Full screen graph of actual high and low pressures and high and low pressure limits A sliding bar enabl...

Page 22: ...ELECTRICAL CONNECTIONS System for Heat Pump Configuration on page 42 System for Heat Recovery Configuration on page 43 DIP Switch Settings For Use With Gen 4 Indoor Units on page 44 ...

Page 23: ...r Outdoor Unit Communication Terminal Block Master Outdoor Unit Communication Terminal Block Slave 1 Outdoor Unit Communication Terminal Block Slave 2 Outdoor Unit Communication Terminal Block IndoorUnit IndoorUnit ODU IDU CENTRAL ODU IDU CENTRAL For Heat Recovery Unit information refer to the applicable Engineering Manual on www lghvac com Figure 9 Example of a Typical Heat Pump Configuration Pow...

Page 24: ...NLY ust be ON System will operate WITH Gen 4 indoor unit features Gen 4 or Higher Gen 4 ONLY odel 2A ONLY OFF System will operate but WITHOUT Gen 4 indoor unit features Gen 4 or Higher Gen 4 ONLY Any combination of odels 1A 2A ust be O factory default Does NOT include Gen 4 features System will not operate if DIP Switch No 3 is ON and an error code will be generated Gen 4 or Higher Any combination...

Page 25: ...WATER LOOP CIRCUIT DESIGN Water Design Guide on page 46 Water Circuit Installation on page 50 ...

Page 26: ...o u r ce U n i t s I n t e r l o ck O p e r a t i o n R o o m 1 R o o m 2 R o o m 3 5 9 F 6 8 F 5 9 F 68 F M e ch a n i ca l R o o m WATER DESIGN GUIDE Water Heating Cycle Diagram WATER DESIGN GUIDE Design Steps A Multi V Water 5 575V system requires a water cooling heating source This year round heating and cooling system must have a two pipe closed loop water circuit that circulates water contin...

Page 27: ...rs in the water loop especially if the water temperature is operated above 104 F Ensure all air is purged from the system Maintain the following levels Item Closed Type System Effect Circulating Water Supplemented Water Corrosion Scale Basic Items pH 77 F 7 0 8 0 7 0 8 0 O O Conductivity 77 F mS m Below 30 Below 30 O O Chlorine ions mg Cl L Below 50 Below 50 O Sulfate ions mg SO4 2 2 L Below 50 Be...

Page 28: ...rly or parts other than those specified by LG are used there is risk of fire electric shock explosion and physical injury or death WARNING WATER CIRCUIT INSTALLATION Pipe Insulation Water pipe insulation is suggested in the following conditions Where water pipe is subject to freezing Water pipe where water can condense on surface of pipe from ambient room temperatures higher than temperature of wa...

Page 29: ...ot share the electrical circuit with other devices There is risk of fire electric shock and physi cal injury or death due to heat generation Do not use damaged or loose power wiring Do not modify or extend the outdoor unit s power wiring randomly Ensure that the power wiring will not be pulled nor weight be placed on the power wiring during operation There is risk of fire electric shock and physi ...

Page 30: ...onnector Flow S witch S erv ice Valv e S erv ice Valv e Valv e Power 24V and Control Pressure G auge Pressure G auge Thermometer Thermometer S hutoff Valv e S hutoff Valv e Condenser Water S upply Condenser Water Return Variable Water Flow Valve Control Kit for Dual Frame Piping System Specifications WATER CIRCUIT INSTALLATION Configuring Variable Water Flow Valve Control Kit for each WSU LG recom...

Page 31: ...Panel Boiler V2 T2 Pump H eat E x changer Plate Ty pe M ulti V Water IV Unit T1 Intermediate Water H eat E x changer Refrigerant Piping System Specifications WATER CIRCUIT INSTALLATION Figure 23 Variable Water Flow Valve Control Kits for Triple Frame S hutoff Valv e 50 M esh S trainer Flex Connector Flow S witch PWFCK N0001 PWFCK N0001 PWFCK N0001 S erv ice Valv e S erv ice Valv e 1 Variable Water...

Page 32: ...PING LIMITATIONS For Systems Designed for Heat Pump Configuration Following pages present Multi V Water V piping limitations and are for illustrative purposes only Designers MUST use LATS when designing LG VRF systems Length Total pipe length Longest actual pipe length Equivalent pipe length1 A ΣB ΣC 1 640 feet 656 feet 738 feet ℓ Longest pipe length after first branch 131 feet 295 feet conditiona...

Page 33: ...ed main pipe A diameters as indicated by outdoor unit capacity Example When an indoor unit combination ratio of 120 is connected to a 20 ton outdoor unit 24 tons and indoor unit with a 7 000 Btu h capacity is located at the first branch 1 ain pipe A diameters on a 20 ton outdoor unit 1 1 8Ø inches vapor and 5 8Ø inches liquid 2 Pipe diameters between first and second branches however are 1 3 8Ø va...

Page 34: ... of the tube Drawn temper rigid ACR copper tubing is available in sizes 3 8 through 2 1 8 inches ASTM B 280 clean dry and capped Annealed temper soft ACR copper tubing is available in sizes 1 4 through 2 1 8 inches ASTM B 280 clean dry and capped Handling the Piping To avoid operation failure a VRF system CANNOT have contaminants or moisture in the piping network Piping must be kept clean dry and ...

Page 35: ...plicable Engineering Manual on www lghvac com WSU Water Source Unit HRU Heat Recovery Unit IDU Indoor Unit A Main Pipe from Water Source Unit to First Y branch B HRU to HRU Y branch to HRU HRU to Header or Y branch to Y branch C Heat Recovery Unit Header to Indoor Unit Example of Pipe Sizing When Installing a Heat Recovery System Example Triple frame system four 4 heat recovery units one 1 header ...

Page 36: ...performances to fluctuate Y branches and other header branches cannot be installed downstream of the initial header branch PIPING LIMITATIONS For Systems Designed for Heat Recovery Configuration Following pages present Multi V Water V piping limitations and are for illustrative purposes only Designers MUST use LATS when designing LG VRF systems Slave 2 Slave 1 Master To Heat Recovery Units A1 A2 A...

Page 37: ...ixed points provisions must be provided to allow pipe expansion to naturally occur generally by expansion Loops or U bends Flaring the Piping When flaring the piping use a dedicated R 410A flaring tool use only synthetic oil between the nut and the flare not inside the piping to achieve correct torque and prevent leaks Flares must be deeper to handle the higher pressures of R 410A When brazing the...

Page 38: ...o not install the unit in a location where acidic solution and spray sulfur are often used as it can cause bodily injury or death Do not use the unit in environments where oil steam or sulfuric gas are present as it can cause bodily injury or death Water source units are not weatherproof Always install water source units indoors Failure to follow this installation guideline can create an electrica...

Page 39: ...isk of the product falling and causing physical injury WARNING Place a protective cloth or other soft material at the locations where the casing comes in contact with the lifting straps to prevent damage to painted surfaces Figure 38 Moving requirements for water source units Water Source Unit s Single Frame Installation Install single frame water source units as shown Anchor bolt locations for in...

Page 40: ...ics Canada Inc if the available space is less than the space shown in these figures If water piping passes along the side of a frame ensure the indicated space is available after considering the space taken by the piping Ensure that the floor chosen location has enough strength to support the weight of the unit s If it does not have sufficient strength the unit s may fall and cause physical injury...

Page 41: ...20001747 ISO 9001 2008 LG ELECTRONICS INC EM_MultiV_WaterV_575V_10_1 LG Electronics Canada Inc Air Conditioning Technologies 20 Norelco Drive North York Ontario M9L2X6 http www lgvrf ca ...

Reviews: