38 | WSU PRODUCT DATA
WSU PRODUCT DATA | 39
W
ater Source Unit Product Data
MUL
TI V W
ater V W
ater Source Unit Engineering Manual
© LG Electronics Canada, Inc., North York, ON Canada. All rights reserved. “LG” is a registered trademark of LG Corp.
© LG Electronics Canada, Inc., North York, ON Canada. All rights reserved. “LG” is a registered trademark of LG Corp.
ACCESSORIES
Unit: Inch
4 branch
ARBL054
7 branch
ARBL057
4 branch
ARBL104
7 branch
ARBL107
10 branch
ARBL1010
10 branch
ARBL2010
Models
Vapor pipe
Liquid pipe
14-3/16
21-1/4
21-1/4
4-3/4
I.D. 5/8
I.D. 1/2
I.D. 1/2
I.D. 5/8
I.D. 5/8
I.D. 3/4
4-3/4
14-3/16
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 1/4
I.D. 3/8
I.D. 1/2
5-15/16
5-15/16
5-15/16
5-15/16
5-15/16
15-3/4
6-5/16
I.D. 5/8
I.D. 1/2
I.D. 3/4
I.D. 5/8
I.D 7/8
I.D. 1-1/8 I.D. 1
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
I.D. 5/8
I.D. 1/2
I.D. 5/8
I.D. 1/2
I.D. 5/8
I.D. 3/4
4-3/4
I.D. 1/4
I.D. 3/8
I.D. 3/8
I.D. 1/2
6-5/16
22-7/8
I.D. 3/4
I.D. 5/8
ID15.88(5/8)
ID12.7(1/2)
I.D. 5/8
I.D. 1/2
I.D. 7/8
I.D. 1-1/8
I.D. 1
27-9/16
4-3/4
I.D. 1/4
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 3/8
I.D. 1/2
I.D. 5/8
I.D. 1/2
4-3/4
28-3/8
I.D. 1/4
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 1/2
I.D. 3/8
4-1/4
21-1/2
27-9/16
I.D. 1/4
I.D. 3/8
I.D. 3/4
I.D. 5/8
I.D. 3/8
I.D. 1/4
4-3/4
4-3/4
6-5/16
29-7/8
I.D. 3/4
I.D. 5/8
I.D. 7/8
I.D. 1-1/8
I.D. 1
7-3/16
30-9/16
I.D. 3/4
I.D. 5/8
I.D. 5/8
I.D. 1/2
I.D. 1-1/8
I.D. 1-1/4
I.D. 1-3/8
5-15/16
5-15/16
5-15/16
5-15/16
5-15/16
5-15/16
5-15/16
4-3/4
4-3/4
14-3/16
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 1/4
I.D. 3/8
I.D. 1/2
Headers for Heat Pump and Heat Recovery Configuration
Headers
ACCESSORIES
• LG headers serve as central connections for multiple runout pipe segments
terminating at indoor units.
• Headers must be used with LG systems and be properly installed following the
instructions in the applicable LG manual. Field-supplied headers are not permitted.
• Kit components must be kept free of debris and dry before installation.
• All Header Kits include:
- Insulation jacket (one each for vapor and liquid pipes)
- Plugging tubes / Insulation for plugging tubes (see Table 26).
Model
Fitting Capacity
Port Capacity
ARBL054 (4 branch)
≤72,000 connected capacity
≤54,300 per port
ARBL057 (7 branch)
≤75,100 connected capacity
≤54,300 per port
ARBL1010 (10 branch)
≤172,200 connected capacity
≤76,300 per port
ARBL104 (4 branch)
≤305,200 connected capacity
≤76,300 per port
ARBL107 (7 branch)
≤534,000 connected capacity
<76,300 per port
ARBL2010 (10 branch)
≤560,000 connected capacity
≤76,300 per port
Table 7: Nominal Capacity Range.
Table 8: Plugging Tubes and Plugging Tube Insulation Amounts.
Header Kits
Plugging Tubes (in OD)
Insulation for Plugging Tubes
1/4
1/2
5/8
ARBL054 (4 port)
—
—
—
—
ARBL057 (7 port)
2
2
—
4
ARBL1010 (10 port)
2
2
2
6
ARBL104 (4 port)
—
—
—
—
ARBL107 (7 port)
2
2
2
6
ARBL2010 (10 port)
2
2
2
6
Table 9: Insulation Jacket Properties.
Material
Polyolefin Foam
UL94 Flame Classification
HF-1
Density
1.84 lbs./ft.
3
Thermal Conductivity
.0208 Btu/h/ft. ºF
Thickness
1/2 inch
Material
Copper
Design Pressure
550 psig
Table 10: Fitting Properties.
Headers
Figure 7: Header.