42
Outside Unit
Electrical Wiring
• Use the 2-core shield cables for transmission lines. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate
power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never
install a phase leading capacitor.
• Keep power imbalance within 2% of the supply rating. Large imbalance will shorten the life of the
smoothing capacitor.
• Introducing with a missing N-phase or with a mistaken N-phase will break the equipment.
WARNING
Control Box and Wiring Location
- Unscrew all the screw, pull out the panel.
- Connect the transmission wire between outside unit and indoor
unit, the connection between outside unit and central controller
system pass through the sub PCB for central control.
- When connecting indoor unit with the shield cable, ground at
the grounding screw.
When connecting central controller with the shield cable,
ground at the grounding screw.
- Refer to next page about the distance between main power
cable and communication cable.
- Refer to page 44 for Auto Addressing and page 47 for Test Run
Front
Panel
2-Core Shield Cable
Multi-Core Cable
Master
Slave1
Slave2
Master
Slave1
Slave2
Remote
controller
Remote
controller
Indoor
Unit
Indoor
Unit
Remote
controller
Outside Unit
Outside Unit
Remote
controller
Indoor
Unit
Indoor
Unit
Master
Slave1
Slave2
Master
Slave1
Slave2
Outside Unit
Outside Unit
Remote
controller
Remote
controller
Indoor
Unit
Indoor
Unit
Remote
controller
Remote
controller
Indoor
Unit
Indoor
Unit
MFL67705803 2018. 9. 17. 오오 12:58 Page 42