After completing work, securely tighten both service ports and caps so that gas does not leak.
Refrigerant piping installation
Always use extreme care to prevent the refrigerant gas (R410A) from leakage while using fire or
flame. If the refrigerant gas comes in contact with the flame from any source, such as a gas stove, it
breaks down and generates a poisonous gas which can cause gas poisoning. Never perform brazing
in an unventilated room. Always conduct an inspection for gas leakage after installation of the refrig-
erant piping has been completed.
Cautions in pipe connection/valve operation
Open status when both the pipe and
the valve are in a straight line.
Do not cutting.
CLOSE
OPEN
Liquid pipe
Gas pipe
h
Remove the front panel before pipe connection
h
Must check the pipe (gas pipe, liquid pipe) before pipe con-
nection
Refrigerant piping installation
WARNING
WARNING