ay Ceiling Cassette Product Data
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
FOUR-WAY CEILING CASSETTE
Electrical Data
Table 31: Four-Way Ceiling Cassette (2' x 2' and 3' x 3' Frames) Indoor Unit Electrical Data.
Model
Voltage Range
MCA
MOP
Rated Amps (A)
Power Supply
Power Input (W)
Hz
Volts
Phase
Cooling
Heating
[)UDPHV
ARNU053TRD4
187-253
0.25
15
0.2
60
208-230
1
30
30
ARNU073TRD4
0.25
0.2
30
30
ARNU093TRD4
0.25
0.2
30
30
ARNU123TRD4
0.25
0.2
30
30
ARNU153TQD4
0.25
0.2
30
30
ARNU183TQD4
0.25
0.2
30
30
[)ULJK
ARNU243TPC4
187-253
0.19
15
0.15
60
208-230
1
33
33
ARNU283TPC4
0.19
0.15
33
33
[)ULJK
ARNU073TNA4
187-253
0.71
15
0.56
60
208-230
1
144
144
ARNU093TNA4
0.71
0.56
144
144
ARNU123TNA4
0.71
0.56
144
144
ARNU153TNA4
0.71
0.56
144
144
ARNU183TNA4
0.71
0.56
144
144
ARNU243TNA4
0.71
0.56
144
144
ARNU363TNC4
0.71
0.56
144
144
[)ULJK
ARNU243TMA4
187-253
1.6
15
1.3
60
208-230
1
144
144
ARNU283TMA4
1.6
1.3
144
144
ARNU363TMA4
1.6
1.3
144
144
ARNU423TMC4
1.6
1.3
144
144
ARNU483TMC4
1.6
1.3
144
144
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of a fuse, use the circuit breaker.