Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using
duct at fan discharge of ODU.
Static pressure compensation mode setting method
FAN Maximum RPM of each step
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn2” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“op1~op3” Push the ‘
●
’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Capacity
UX2
UX3
0~20Pa
Standard
730
950
20~40Pa
op1
800
1020
40~60Pa
op2
820
1050
60~80Pa
op3
850
1110