PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
33
ENGLISH
3 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN31
Ⓕ
: Connection branch pipe between Outdoor
units: ARCNN21
4 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN41
Ⓕ
: Connection branch pipe between Outdoor
units: ARCNN31
Ⓖ
: Connection branch pipe between Outdoor
units : ARCNN21
10m or
less
H 110m
L 200m
40m
Master
Slave2
Slave1
ODU Capacity
Master ≥ Slave1 ≥ Slave2
40m
h1
Branch pipe can not be used after header
Branch pipe can not be used after header
10m or
less
H 110m
L 200m
40m
Master
Slave3
Slave1
Slave2
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
40m
G
G
h1
F
E
F
E
Total pipe length = A+a+b+c+d+e+f
≤
1,000m
L
Longest pipe length
*Equivalent pipe length
A+f
≤
200m
A+f
≤
225m
l
Longest pipe length after 1st branch
f
≤
40m
H
Difference in height (Outdoor Unit
÷
Indoor Unit)
H
≤
110m
h
Difference in height (Indoor Unit
÷
Indoor Unit)
h
≤
40m
h1
Difference in height (Outdoor Unit
÷
Outdoor Unit)
h1
≤
5m