4. Trouble Shooting
- 120 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
61
62
Condenser pipe sensor
temp. high
Heat sink sensor
temp. high
• Condenser pipe sensor
detected high
temp.(65°C)
• Heat sink sensor detect-
ed high temp.(85°C)
• Check the load condition.
• Check the sensor of Condenser pipe sensor.
• Check the Heat sink sensor (10k
Ω
±10% at 25°C)
• Check that outdoor fan is driving rightly
Display
code
Title
Cause of error
Check point & Normal condition
Comp frequecy control accoding to heatsink temp.
ქኩ༯
ZGy\
Ⴓ
ქኩ༯
Ⴓ
ქኩ༯
໎ཙ
ხᄅ
ጒ
ხᄅ
α
Gy
Cnvm
α
Gy
Cnvm
α
Gy
Cnvm
NEE
Snee
8/
°
C
S1
74
°
C
S0
7/
°
C
Gd`sRhmjပ
■
Comp frequency control according to heat sink temp.
No
Is normal heatsink sensor
connecting ?
No
Connect the heatsink sensor right
Replace the heatsink sensor
No
Replace the heatsink sensor
Yes
Yes
Recheck power and
installation condition
Is normal heatsink sensor ?
(10k
Ω
±
10% at 25
°
C)
Yes
Is normal Inverter PCB ?