4. Trouble Shooting
- 111 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Check Point
1. Check the Tab1 connection condition. (Refer to outdoor wiring diagram)
2. Check the CN_L1(R), CN_L2(S), CN_L3(T) connection condition
3. Check the DC Link voltage at not operating(380V
↑
)
4. Check the DC Link voltage at Comp operating(500V
↑
)
5. Check DC Link Sensing Signal (Refer the Picture)
<INVERTER PCB>
<DC Link Voltage Check Point>
+
GND
500Vdc
±
10%
DC Link
DC Link Voltage INV
oltage INV
<INPUT VOLTAGE Check Point>
GND
GND
DC Link Voltage INV
GND
Vdc
Tester
Summary of Contents for Multi-Inverter Type
Page 123: ...P NO MFL36552501 APRIL 2008 ...