Part 2 Functions & Controls
- 21 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Static pressure(mmAq)
Setting value
0
1
2
Model name
Step(Hi/Med/Lo)
8 CMM
220
215
210
7 CMM
240
235
230
6 CMM
255
250
245
10 CMM
210
85
150
9 CMM
215
190
170
8 CMM
220
200
175
14 CMM
170
150
130
13 CMM
185
165
145
12 CMM
200
180
160
AMNH096BTG0
[MB09AHL NT0]
AMNH126BTG0
[MB12AHL NT0]
AMNH186BTG0
[MB18AHL NT0]
Static pressure(mmAq)
Setting value
0
1
2
3
4
Model name
Step(Hi/Med/Lo)
8.5 CMM
75
84
94
104
114
7.5 CMM
69
77
88
99
110
6.5 CMM
62
71
83
95
106
9.5 CMM
82
90
99
109
118
8.5 CMM
75
84
94
104
114
7.5 CMM
69
77
88
99
110
15 CMM
90
97
105
114
122
13.5 CMM
82
90
99
109
119
11.5 CMM
75
84
93
103
114
17 CMM
110
117
125
129
-
15 CMM
100
107
115
121
127
13.5 CMM
90
97
105
114
122
AMNH09GB1A0/1
[MB09AHL N10/1]
AMNH12GB1A0/1
[MB12AHL N10/1]
AMNH18GB2A0/1
[MB18AHL N20/1]
AMNH24GB2A0/1
[MB24AHL N20/1]
E.S.P. setting value (reference)
Static pressure(mmAq)
0
2
4
Model name Step(Hi/Med/Lo)
Setting value
10.5CMM
225
220
210
AMNH096BPA0
9CMM
245
240
230
8.5CMM
254
253
250
11.5CMM
210
200
100
AMNH126BPA0
10CMM
235
230
220
8.5CMM
254
251
245
[ Notes ]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.