Paramet
er
Address
Parameter Name
Unit
Read/Write
Data Value (Hex)
0x0010
Input Terminal
Status
-
R
Bit 0: P1, Bit 1: P2, Bit 2: P3
Bit 3: P4, Bit 4: P5, Bit 5:
P6,
Bit 6: RST, Bit 7: BX, Bit 8:
JOG, Bit 9: FX, Bit 10: RX
0x0011
Output Terminal
Status
-
R
Bit 0: Q1 (OC1), Bit 1: Q2
(OC2) Bit 2: Q3 (OC3), Bit
3: AUX Bit 4: 30AC
0x0012
V1
-
R
0 – FFC0
0x0013
V2
-
R
0 – FFC0
0x0014
I
-
R
0 – FFC0
0x0015
RPM
-
R
(Note 3)
The changed value in Common affects the current setting but returns to the previous setting when
power is cycled or Inverter is reset. However, changing value is immediately reflected in other parameter groups
even in the case of Reset or Power On/Off.
< DRV Group >
Addre
ss
NO.
Description
Default
Maximu
m
Minimum
Unit
5100
DRV#00
Cmd. freq
0
MaxFre
q
0
0.01Hz
5101
DRV#01
Acc. Time
100
6000
0
0.1sec
5102
DRV#02
Dec. Time
200
6000
0
0.1sec
11