Paramet
er
Address
Parameter Name
Unit
Read/Write
Data Value (Hex)
0x000A
Output Frequency
0.01 Hz
R
0x000B
Output Voltage
0.1 V
R
0x000C
DC Link Voltage
0.1 V
R
0x000D
Output Power
0.1 kW
R
0x000E
Sequence Monitor
-
R
BIT 0 : Stop
BIT 1 : Forward Run
BIT 2 : Reverse Run
BIT 3 : Fault (Trip)
BIT 4 : Accelerating
BIT 5 : Decelerating
BIT 6 : Output Frequency
Arrival
BIT 7 : DC Braking
BIT 8 : Stopping
BIT 9 :Not Available
BIT 10 : BrakeOpen
BIT11: Forward Run
Command
BIT 12 : Reverse Run
Command
0x000F
Trip information
-
R
Bit 0:OCT1, Bit 1: OV, Bit 2:
EXT-A Bit 3: BX, Bit
4:OCT2, Bit 5: GF, Bit 6:
OH, Bit 7: ETH, Bit 8: OLT,
Bit 9: HW-diag, Bit10:EXT-
B, Bit11:FO Bit12:OPT,
Bit13:PO
Bit,14:IOLT,
Bit15:LV
modbus-rtu iS5 manual.doc 10