28
Ventilator
Installer Setting Code and Value Table
■
Test Run
1. Function explanation: when installing the product, test operation for checking the installation sta-
tus
2. When setting test operation, LCD Display
2.1) cooling, normal, super-high mode, temperature setting 88Seg 'LO', extra operation
2.2) when setting test operation, after test operating for 18 minutes, auto cancellation
2.3) during test operation, extra operation control available (including ventilation KIT)
■
Setting Address of Central Control
1. Function explanation: when connecting central control, it sets the address of central control
address of indoor unit.
2. Function control and setting
2.1) Select the address code with inputting the up-down button. (0~F)
2.2) Change the items with inputting the right-left button.
(Group address
↔
indoor unit address)
2.3) Set the address with inputting Setting/Cancel button.(Indoor data send)
※
DX : Direct expansion ventilation
General : General ventilation
No.
Function
Code
Available Product
Value
1
Test run
01
DX
01: Test run setting
2
Setting Address of
02
General/DX
00~FF : Address of central control
Central Control
3
Supply ESP
03
General/DX
Value1 – Step(01:low, 02:high, 03:super high)
4
Exhaust ESP
04
Value2 – ESP value(0~255)
5
Product direction
05
General
01:Normal, 02:Reverse
6
Quick Refresh Priority
06
General/DX
01:Supply air first, 02:Exhaust air first
7
Master setting
07
General/DX
00:Slave, 01:Master
8
Override setting
08
DX
00:Slave, 01:Master
9
Dry Contact Auto
09
General/DX
00:OFF, 01:ON
10
Release of 3Min. Delay
10
General/DX
01:Set
11
Zone State
11
DX
01:Variable, 02:Fixed
12
Selecting °C or F
12
DX
00:Celsius , 01:Fahrenheit
13
Humidification for
13
DX
00 : Not in use
Singlar Ventilation
01 : Use
14
Humidification for
14
DX
01:Automatic, 02:Manual
Heat Mode Ventilation
Field Setting and Test Run