16 Room Air Conditioner
Flaring work and connection of piping
3. Tape the tubing, drain hose and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper side
can cause drain pan to overflow inside the unit.
3. Tape the tubing, drain hose and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper side
can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material*
so that dripping from "sweating"(condensa-
tion) will not damage furniture or floors.
*Foamed polyethylene or equivalent is rec-
ommended.
4. Indoor unit installation
■
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the three hooks of the
rear top and rear lower of the indoor unit with the
upper edge and lower edge of the installation
plate.) Ensure that the hooks are properly seated
on the installation plate by moving it left and right.
5. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
■
Align the center of the pipings and sufficiently
tighten the flare nut by hand.
■
Tighten the flare nut with a wrench.
■
When extending the drain hose at the indoor unit,
install the drain pipe.
Connecting
cable
Loop
Gas side
piping
Liquid side
piping
Drain hose
Installation
plate
Three upper
hooks
Installation plate
Indoor unit
Three lower
hooks
Setting line
Indoor unit tubing
Flare nut
Pipings
Connection pipe
Flare nut
Indoor unit tubing
Torque wrench
Spanner (fixed)
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Pipe Size[Torque]
Capacity
(Btu/h)
Suction
Evaporator
30K
5/8"[6.6kg.m]
3/8"[4.2kg.m]