background image

-29-

2) Connect the cable to the outdoor unit

1. Remove the control cover from the unit by loos-

ening the screw.
Connect the wires to the terminals on the control
board individually.

2. Secure the cable onto the control board with the

cord clamp.

3. Refix the control cover to the original position

with the screw.

4. Use a recognized circuit breaker "A" 

between the power source and the unit. 
A disconnecting device to adequately disconnect
all supply lines must be fitted.

Terminal block

Over 5mm

Cover control

Connecting cable

Connecting cable

After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of

wiring, be guided by the circuit diagram posted on the inside of control cover.

2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from

vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)

3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on

the name plate.

6) Confirm that the cable thickness is as specified in the power source specification.

(Particularly note the relation between cable length and thickness. (Refer to page 28))

7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.

• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal

function of the overload.

9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an

air gap contact separation of at least 3mm in each active(phase) conductors.

Outdoor Unit

CAUTION

7k~14k

18k

24k~28k 30k, 32k 36k, 38k

15

20

30

30

40

Circuit

Breaker

(A)

Grade

Summary of Contents for LS-C076Z Series

Page 1: ...onditioner CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORIZED SERVICE PERSONNEL MODEL LS H096Z_Series LS H076Z_Series LS C096Z_Series LS C076Z_Series WEBSITE http biz LGservice com ...

Page 2: ...ng Diagram 12 Operation Details 13 Display Function 20 Installation 21 Operation 34 Disassembly of the parts Indoor Unit 35 2 way 3 way Valve 38 Cycle Troubleshooting Guide 46 Electronic Parts Troubleshooting Guide 47 Electronic Control Device 56 Schematic Diagram 59 Exploded View and Replacement Parts List 60 2 ...

Page 3: ...60Hz 8 380 415V 50Hz 9 380 415V 60Hz 7 Chassis A Z Name of Chassis of Unit Ex LSP SP Chassis 8 Look A Z Look Color Artcool Model 9 Function A Z 10 Serial No 1 9 LG Model De ARTCOOL COLOR velopment Serial No Basic A Basic 4Way B Plasma Filter C Plasma Filter 4 Way D Tele LCD E Tele LCD Nano plasma 4Way F Nano Plasma F A changeove A clean Low A G Nano Plasma F A changeove A clean 4way Low A H Tele L...

Page 4: ...set at the desired position or swing up and down automatically Indoor Unit Operation ON OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Time Delay Safety Control Indoor Fan Speed Control Soft Dry Operation Mode The function will be operated while in any operation mode with selecting the function The function is to be stopped while it is opera...

Page 5: ...Auto Cleaning Mode Lights up during Auto Cleaning reservation Jet Cool Mode Lights up during Jet Cool Operation Plasma Lights up during Plasma operation Fan Speed Low Lights up when Fan speed is low Fan Speed Medium Lights up when Fan speed is Medium Fan Speed High Lights up when Fan speed is High Fan Speed Chaos Lights up when Fan speed is Chaos Desire temperature For cooling dehumidification hea...

Page 6: ...Operation Mode Heating Operation Mode Auto Operation Mode Air Circulation Horizontal Airflow Direction Control Button Optional Room Temperature Checking Setting the Time or Timer PLASMA Optional Fan Speed Selection Low Med High ON OFF CANCEL SET 2nd F AUTO CLEAN LED LUMINOSITY AUTO CLEAN High 39 C Low 11 C OFF ON OFF ON Cancel Sleep Mode Timer ON or Timer OFF 1 2 3 4 5 6 7 Off Timer Fan Operates w...

Page 7: ... refer to Label Quality on the product since this specification may be changed for improving performance 9 000 7 000 9 000 7 000 9 300 7 300 1 1 1 1 1Ø 220 240V 50Hz 1Ø 220 240V 50Hz 1Ø 220 240V 50Hz 1Ø 220 240V 50Hz 6 8 5 7 6 8 5 7 26 20 20 20 35 32 35 32 48 48 48 48 940 700 940 650 850 628 4 2 3 2 4 2 2 9 3 8 2 9 9 57 10 9 57 10 77 3 2 3 4 7 8 4 7 7 8 4 7 27 18 18 18 900 x 272 x 135 900 x 272 x ...

Page 8: ... 8 Installation plate D H W MODEL DIM Unit W mm 900 H mm 272 D mm 135 7K 9K Btu Series Dimensions 1 Indoor Unit ...

Page 9: ... L1 D H L4 L5 Gas side 3 way valve Liquid side 2 way valve MODEL DIM unit W mm 770 564 H mm 540 525 D mm 245 265 L1 mm 287 294 L2 mm 64 66 L3 mm 518 374 L4 mm 10 17 L5 mm 100 270 LS H096Z_Series LS C096Z_Series LS C076Z_Series ...

Page 10: ... 10 W L2 L3 L1 D H L4 L5 Gas side 3 way valve Liquid side 2 way valve MODEL DIM Unit W mm 575 H mm 525 D mm 260 L1 mm 301 L2 mm 73 L3 mm 392 L4 mm 35 L5 mm 100 LS H076Z_Series ...

Page 11: ...XCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER HEAT EXCHANGE CONDENSER COMPRESSOR COMPRESSOR ACCUMU LATOR GAS SIDE GAS SIDE VALVE LIQUID SIDE LIQUID SIDE VALVE CAPILLARY TUBE CAPILLARY TUBE CHECK VALVE Heating Model only COOLING HEATING REVERSING VALVE Heating Model Only 1 Cooling Only Models 2 Cooling Heating Models ...

Page 12: ...N YL 1 L 2 N 3 4 3 4 BL BR CN U D WH CN DISP1 STEP MOTOR CN L R BL CN HVB STEP MOTOR OPTION OPTION LIMIT S W 1 LIMIT S W 2 H V B A CL RD RD BK BK SUC STEP MOTOR 2 3854A20238Y INDOOR WIRING DIAGRAM FUSE AC250V T2A CN TH1 TRIAC SH CAPA BL BR GN YL BR YL OR BK CN TAB1 CN MOTOR CN TAB2 CN SW 2 CN SW 3 CN STEP2 CN STEP1 CN MAIN CN SW 1 RY COMP FORCED OPERATON S W SUC STEP MOTOR 1 ZNR THERMISTOR DISPLAY...

Page 13: ...r ON while in timer mode on off OFF when timer mode is completed or canceled Defrost Indicator OFF except when hot start during heating mode operation or while in defrost control Cooling Mode Operation When the intake air temperature reaches 0 5 C below the setting temp the compressor and the outdoor fan stop When it reaches 0 5 C above the setting temp they start to operate again Compressor ON Te...

Page 14: ...rry out defrost control or not and the time of defrost control are determined according to the following conditions 1 While in heating mode operation the maximum of the indoor pipe temperature is measured and it is com pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures the maximum temperature of indoor pipe the present temperature of indoor pipe ac...

Page 15: ...oor fan is operated for 15 seconds Then an operation mode is selected according to the intake air temp at that moment as follows 24 C Inatake Air Temp Fuzzy Operation for Cooling 21 C Inatake Air Temp 24 C Fuzzy Operation for Dehumidification Inatake Air Temp 21 C Fuzzy Operation for Heating If any of the operation modes among cooling dehumidification heating mode operations is carried out for 10 ...

Page 16: ...d by Fuzzy rule when the intake air temp is 3 C or more above the setting temp the compressor is turned off When below the setting temp the compressor is turned on Compressor ON Temp Setting Temp Compressor OFF Temp Setting Temp 3 C At the beginning of Fuzzy mode operation the setting temperature is automatically selected according to the intake air temp at that time 20 C Intake Air Temp Intake Ai...

Page 17: ... cannot be input While in cooling mode operation 30 min later since the start of the sleep timer the setting temperature increases by 1 C After another 30 min elapse it increases by 1 C again When the sleep timer mode is input while in cooling cycle mode the airflow speed of the indoor fan is set to the low When the sleep timer mode is input while in heating cycle mode the airflow speed of the ind...

Page 18: ...s pressed If you want to stop operation re press the button While in forced operation the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation Test operation During the TEST OPERATION the unit operates in cooling mode at high speed fan regardless of room tem perature and resets in 18 1 minutes During test operation if remote controller signa...

Page 19: ... of the room temperature Auto Clean Open the door on the remote control Press the Auto Clean Button Close the door on the remote control Now each time that you press the start stop button the Air conditioner operates clean function automatically Display Luminosity The Display Luminosity can be adjusted by using the remote control Press the start stop button to start the unit Open the door on the r...

Page 20: ...peration Auto Cleaning Mode Lights up during Auto Cleaning reservation Jet Cool Mode Lights up during Jet Cool Operation Plasma Lights up during Plasma operation Fan Speed Low Lights up when Fan speed is low Fan Speed Medium Lights up when Fan speed is Medium Fan Speed High Lights up when Fan speed is High Fan Speed Chaos Lights up when Fan speed is Chaos Desire temperature For cooling dehumidific...

Page 21: ...the path of the warm air Take the air conditioner weight into account and select a place where noise and vibration are minimum Select a place so that the warm air and noise from the air conditioner do not disturb neighbors 2 Piping length and elevation Installation 1 Installation of indoor Outdoor unit 21 More than A More than B More than 2 3m More than B More than 10cm More than 10cm More than 60...

Page 22: ...use caution concerning the location of the installation plate routing of the wiring to power outlets is through the walls typi cally Drilling the hole through the wall for piping connections must be done safely 4 Drill a hole in the wall Drill the piping hole with a ø70mm hole core drill Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side 22 Ins...

Page 23: ... put them on after flaring work 4 Flaring work Firmly hold copper pipe in a die in the dimension shown in the table above Carry out flaring work using flaring tool as shown below 5 Check Compare the flared work with figure below If flare is noted to be defective cut off the flared sec tion and re flare it 2 Connection of piping Indoor Preparing the indoor unit s piping and drain hose for installat...

Page 24: ... right Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 4 Connecting the pipings to the indoor unit and drain hose to drain pipe Align the center of the pipes and sufficiently tighten the flare nut by hand Tighten the flare nut with a wrench When extending the drain hose at the indoor unit install the drain pipe ...

Page 25: ...ndoor unit from the wall 6 Connecting the pipings to the indoor unit and the drain hose to drain pipe Align the center of the pipes and sufficiently tighten the flare nut by hand Tighten the flare nut with a wrench When extending the drain hose at the indoor unit install the drain pipe 7 Wrap the insulation material around the con necting portion Overlap the connection pipe heat insulation and the...

Page 26: ...llation Remove the spacer Ensure that the hooks are properly seated on the installation plate by moving it left and right Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 26 Vinyl tape narrow Connection pipe Connecting cable Indoor unit piping Pipe Vinyl tape wide Wrap with vinyl tape Drain hose Connecting cable ...

Page 27: ...tening the flare nut with torque wrench ensure the direction for tightening follows the arrow on the wrench mm inch kg m Ø6 35 1 4 1 8 Ø9 52 3 8 4 2 Ø12 7 1 2 5 5 Ø15 88 5 8 6 6 Ø19 05 3 4 6 6 Outside diameter Torque Outdoor unit Gas side piping Bigger diameter Liquid side piping Smaller diameter Torque wrench Bad case Following bending type from right to left could cause problem of pipe damage CA...

Page 28: ...t should be complied with the following specifications Type B approved by HAR or SAA mm2 mm2 The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications Type B approved by HAR or SAA NORMAL CROSS SECTIONAL AREA 0 75mm2 The above circuit diagram is subject to change with out notice Be sure to connect wires according to the wiring dia gram...

Page 29: ... from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could cause burn out of the wires 3 Specification of power source 4 Confirm that electrical capacity is sufficient 5 See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate 6...

Page 30: ...ground Secure the drain hose appropriately 2 In cases where the outdoor unit is installed below the indoor unit perform the following Tape the piping drain hose and connecting cable from down to up Secure the tapped piping along the exterior wall using saddle or equivalent 3 In cases where the Outdoor unit is installed above the Indoor unit perform the following Tape the piping and connecting cabl...

Page 31: ...re gauges and dry nitrogen gas cylinder to this service port with charge hoses Pressurize the system to no more than 150 P S I G with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P S I G Next test for leaks with liquid soap Do a leak test of all joints of the tubing both indoor and outdoor and both gas and liquid side service valves Bubbles indicate a leak Be su...

Page 32: ... the manifold valve and stop the vacuum pump 4 Finishing the job With a service valve wrench turn the valve stem of liq uid side valve counter clockwise to fully open the valve Turn the valve stem of gas side valve counter clock wise to fully open the valve Loosen the charge hose connected to the gas side service port slightly to release the pressure then remove the hose Replace the flare nut and ...

Page 33: ...ce the gas side pressure of optimum con dition is as below Cooling NOTE If the actual pressure is higher than shown the system is most likely over charged and charge should be removed If the actual pressure are lower than shown the system is most likely undercharged and charge should be added The air conditioner is now ready for use Bolt Tubing connection Discharge temperature Discharge air Intake...

Page 34: ...TON Used to stop or start louver movement and set the desired up down airflow direction ON OFF TIMER BUTTONS Used to set the time of starting and stopping operation TIME SETTING BUTTONS Used to adjust the time TIMER SET CANCEL BUTTON Used to set the timer when the desired time is obtained and to cancel the Timer operation SLEEP MODE AUTO BUTTON Used to set Sleep Mode Auto operation AIR CIRCULATION...

Page 35: ... remove the Grille from the Chassis Hold up Inlet Grille Horizentally To remove the Grille pull the lower left and right side of the grille toward you slightly tilted and lift it straight upward To seperate connecter assembly and than to remove Inlet Grille assembly 1 Before removing the control box be sure to take out the wire screwed at the other end ...

Page 36: ...ox out from the chassis careful ly 3 To remove the Discharge Grille Unhook the discharge grille and pull the dis charge grille out from the chassis carefully 4 To remove the Evaporator Remove 3 screws securing the evaporator at the left 2EA in the Eva Holder at the right 1EA ...

Page 37: ...emove 2 securing screw Pull the motor cover out from the chassis carefully 6 To remove the Cross Flow Fan Loosen the screw securing the cross flow fan to the fan motor do not remove Lift up the right side of the cross flow fan and the fan motor separate the fan motor from the cross flow fan Remove the left end of the cross flow fan from the self aligning bearing Motor cover ...

Page 38: ... gauge Open Open Open with charging cylinder Open Open Open with charging cylinder Open Open Open Open Works Shipping Air purging Installation Operation Pumping down Transfering Evacuation Servicing Gas charging Servicing Pressure check Servicing Gas releasing Servicing 1 2 3 4 5 6 Valve cap Open position Closed position Pin Service port Service port cap To outdoor unit Flare nut To piping connect...

Page 39: ...sing the hexagonal wrench to press the valve core pin discharge for three seconds and then wait for one minute Repeat this three times 5 Use torque wrench to tighten the service port nut to a torque of 1 8kg cm 6 Set the 3 way valve to the back seat 7 Mount the valve stem nuts to the 2 way and 3 way valves 8 Check for gas leakage At this time especially check for gas leakage from the 2 way and 3 w...

Page 40: ...ere 5 Set the 2 way valve to the closed position 6 Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg cm2 g 7 Immediately set the 3 way valve to the closed position Do this quickly so that the gauge ends up indi cating 3 to 5kg cm2 g 8 Disconnect the charge set and mount the 2 way and 3 way valve s stem nuts and the ser vice port nut Use torque wrench to tigh...

Page 41: ... on the 2 way valve 4 Check for gas leakage Check the flare connections for gas leakage 5 Discharge the refrigerant Close the valve on the gas cylinder and dis charge the refrigerant until the gauge indicates 3 to 5 kg cm2 g 6 Disconnect the charge set and the gas cylin der and set the 2 way and 3 way valves to the open position Be sure to use a hexagonal wrench to operate the valve stems 7 Mount ...

Page 42: ...and discharge the refrigerant until the gauge indicates 0 kg cm2 G If there is no air in the refrigerant cycle the pressure when the air conditioner is not run ning is higher than 1 kg cm2 G discharge the refrigerant until the gauge indicates 0 5 to 1 kg cm2 G if this is the case it will not be neces sary to apply a evacuatin Discharge the refrigerant gradually if it is dis charged too suddenly th...

Page 43: ...the vacuum pump and confirm that the gauge needle does not move approxima tely 5 minutes after turning off the vacuum pump 4 Disconnect the charge hose from the vacuum pump Vacuum pump oil If the vacuum pump oil becomes dirty or depleted replenish as needed Lo Open Open Vacuum pump 2 Way valve Outdoor unit Liquid side Indoor unit Gas side 3 Way valve CLOSE OPEN CAUTION Use vacuum pump equipped wit...

Page 44: ...onditioner in the cooling cycle however one time is not suffi cient wait approximately 1 minute and then repeat the procedure pumping down pin 4 Immediately disconnect the charge hose from the 3 way valve s service port Stopping partway will allow the gas to be dis charged If the system has been charged with liquid refriger ant while operating the air conditioner turn off the air conditioner befor...

Page 45: ...ind outdoor temperature Find indoor temperature onto the curve of outdoor temperature Read suction pressure at the axis of ordinates The method of using equation Calculate suction pressure after putting indoor and outdoor temperature into the equation 13 At operating the Unit for 10 minutes Suction Pressure Kg cm 2 g Outdoor Temp C Indoor Temp C 12 11 10 9 8 7 6 5 5 10 15 20 25 30 35 40 50 C 40 C ...

Page 46: ...air humidity is relativery higher temperature difference is smaller When the room air humidity is relatively lower tem perature difference is larger 2 Check temperature and pressure of refrigeration cycle Notice 1 The suction pressure is usually R 22 4 5 6 0 kg cm2 G Cooling at normal condition R 410a 7 2 9 6 kg cm2 G Cooling at normal condition 2 The temperature can be measured by attaching the t...

Page 47: ...R01J ZNR02J Check the connection housing for contacting Connector related to CN TAB1 RY COMP NO 3 Connector related to CN MOTOR Connector contacting of Outdoor Fan Compressor Display PWB Assembly Check Check each load Indoor Outdoor Fan Motor Com pressor Stepping Motor and contacting condition of related connector Main PCB Board Operation Check Items SMPS Transformer Indoor unit Input Voltage Outp...

Page 48: ...tery Check the contact of CN VFD WH connector When the compressor stopped Indoor Fan is driven by a low speed At this point the wind speed is not controlled by the remote controller When operated in the Sleeping Mode the wind speed is set to the low speed by force Check Display PWB Assembly Voltage between CN VFD WH DC 5V Check the connecting circuit between the remote controller MICOM No R17 2Ω I...

Page 49: ...sor Outdoor Fan is stopped Check the related circuit of RY FAN Check the indoor temperature sensor is disconnected or not About 10kΩ at 25 C Turn off Main Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Out door Fan Motor Check the open or short of conmecting wires between indoor and outdoor Check Relay RY COMP for driving comp...

Page 50: ...ircuit of indoor Fan Motor The pin NO 58 of Micom and the part for driving TRIAC the input and output signal of IC01M PIN NO 7 10 Check the pattern Check the TRIAC TRIAC Open Indoor Fan Motor never operate TRIAC short Indoor Fan Motor always operates in case of ON or OFF 4 When indoor Fan does not operate The voltage of PIN NO 1 Black and 3 Black of CN MOTOR About AC 180V over About AC 50V below T...

Page 51: ...D Connector If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the up down Vertical Louver 5 When up down Vertical Louver does not operate Check the up down operating circuit of the Vertical Louver Confirm that there is DC 12V between pin Gray of CN U D and GND Confirm that there is a soldering short at foll...

Page 52: ...Connector If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the left right Vertical Louver 6 When left right Vertical Louver does not operate Check the left right operating circuit of the Vertical Louver Confirm that there is DC 12V between pin Gray of CN L R and GND Confirm that there is a soldering short ...

Page 53: ...B of CN SUC Connector If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Inlet Grille 7 When Inlet Grille does not operate Check the operating circuit of the Inlet Grille Confirm that there is DC 12V between pin RED of CN SUC and GND Confirm that there is a soldering short at following terminals Between ...

Page 54: ...d or not about 10KΩ at 25 C Check the indoor pipe temperature is disconnected or not about 5KΩ at 25 C Turn ON Main Power Check the DC voltage on the PWB ASSEMBLY The details of check are as followings Check point Between Micom NO 59 and GND Between IC01M NO 11 and GND Comp ON DC 5V Below DC 1V Comp OFF DC 0V About DC 12V Check point Between Micom NO 52 and GND Between IC02M NO 11 and GND 4 way ON...

Page 55: ...in Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Out door Fan Motor 4 way Check the open or short of connecting wires between indoor and outdoor ...

Page 56: ... 56 Electronic Control Device 1 MAIN P W B ASSEMBLY AC DC PARTS TOP VIEW 1 MAIN P W B ASM AC BOTTOM VIEW ...

Page 57: ...03A TOP VIEW SEJIN ELECTRON INC SVM GP1119AI P N 3210018043 1 REV1 C13 C7 C8 C9 D1 Q1 Q2 R9 R13 R2 R6 R7 R8 R10 TP1 TP2 TP3 TP4 R17 R18 R19 C14 C15 C18 R4 R3 TP5 TP6 M42 M43 C19 C20 C21 R5 M45 M44 TP1 TP2 TP3 TP4 TP7 TP8 BOTTOM VIEW ...

Page 58: ...RAICS SM1L43 100 1 2W R01J 120 1 2W R02J TR01J T1 1 4W R04J 560 ZNR02J TVR10561 TLP762JF IC01J 1 2 3 5 4 3 3 2 1 2 1 CN MOTOR FAN INDOOR MOTOR KID65004AF 1 UPD780023AGC C Vss0 5V Vdd0 8 NEC X2 Vss1 X1 INT0 INT1 BL 2 3 4 6 5 7 11 4WAY FAN 14 15 16 2 1 13 12 5 6 4 3 IC02M 10 9 7 8 12V OR YL RD PK 4 4 2 2 3 3 1 1 5 5 CN L R BL CSTS0800MG03 T2 R02A 20K 1M 5V R01B CRTL8 00MSOT OSC01B 3 1 Q01C 2SC5343 K...

Page 59: ...ndoor Unit 352150 354210 159901 249951 266090 W0CZZ 733010 263230 346810 131410 146811 1 135311 237900 668713 2 W6631 135314 342800 267110 359011 159830 146811 268712 668713 1 135312 146811 145200 152302 135080 1 135080 2 135516 268714 35211B 264110 ...

Page 60: ...EMBLY 5983A10009B 5983A10009B 5983A10009B 5983A10009B R 159901 VANE HORIZONTAL 5990A20022B 5990A20022B 5990A20022B 5990A20022B R 237900 WINDOW DISPLAY 3790A20037F 3790A20037F 3790A20037F 3790A20037F R 249951 CONTROL BOX ASSEMBLY INDOOR 4995A20323A 4995A20323B 4995A20323F 4995A20323C R 263020 DIGITRON 6302A90003A 6302A90003A 6302A90003A 6302A90003A R 263230 THERMISTOR ASSEMBLY 6323A20004A 6323A2000...

Page 61: ... 263230 THERMISTOR ASSEMBLY 6323A20004A R W0CZZ CAPACITOR DRAWING 3H01487A R 266090 H V ASSEMBLY 6609A10005E R 135312 GRILLE ASSEMBLY FRONT INDOOR 3531A10221Q R 135314 GRILLE ASSEMBLY INLET 3531A20196F R 237900 WINDOW DISPLAY 3790A20083A R 268712 PWB PCB ASSEMBLY DISPLAY 6871A20463A R 135080 1 DECORATION 3508A20055B R 135080 2 DECORATION 3508A20056B R 152302 FILTER MECH A C 5230A20033A R 145200 LI...

Page 62: ... 62 2 1 Outdoor unit 554031 437212 435511 W0CZZ 552202 567502 552116 552102 1 552201 554160 561410 552111 550140 552203 1 552203 2 430410 447910 649950 552102 2 437210 559010 546810 435301 ...

Page 63: ...2102 1 TUBE CAPILLARY BEND 5210A21341A 5424AR3582H 5210A30151R R 552102 2 TUBE CAPILLARY BEND 5424AR7208M R 552111 TUBE ASSEMBLY CAPILLARY 5211A20117G 5211A30275D 5211A30082W R 552116 TUBE ASSEMBLY REVERSING 5211A20116D R 552201 VALVE CHECK 3H01552F R 552202 VALVE REVERSING 5220AR3084A R 552203 1 VALVE SERVICE 2H02479H 2H02479F 2H02479F R 552203 2 VALVE SERVICE 2A00393U 2A00393U 2A00393M R 554031 ...

Page 64: ...CA R 550140 ISOLATOR COMP 4H00982E R 567502 O L P 6750U L014A R 552116 TUBE ASSEMBLY REVERSING 5211A21027A R 552202 VALVE REVERSING 5220AR3084A R 552111 TUBE ASSEMBLY CAPILLARY 5211A10402A R 552201 VALVE CHECK 3H01552C R 552102 1 TUBE CAPILLARY BEND 5210A30151Q R 552102 2 TUBE CAPILLARY BEND 5210A22261A R 649950 CONTROL BOX ASSEMBLY OUTDOOR 4995A90162A R W0CZZ CAPACITOR DRAWING 6120AR2194H R 56141...

Page 65: ... 65 2 2 Outdoor unit 554031 437212 435511 W0CZZ 552202 567502 552116 552102 1 552201 554160 561410 552111 437210 550140 552203 1 552203 2 430410 447910 649950 552102 2 559010 546810 435512 ...

Page 66: ...ILLARY BEND 5210A22261A R 552111 TUBE ASSEMBLY CAPILLARY 5211A10402A R 552116 TUBE ASSEMBLY REVERSING 5211A21027A R 552201 VALVE CHECK 3H01552C R 552202 VALVE REVERSING 5220AR3084A R 552203 1 VALVE SERVICE 2H02479H R 552203 2 VALVE SERVICE 2A00393U R 554031 CONDENSER ASSEMBLY BENT 2403A20059F R 554160 COMPRESSOR SET 2520UCDK028 R 559010 FAN ASSEMBLY PROPELLER 5900AR1266A R 561410 COIL ASSEMBLY REV...

Page 67: ...MEMO 67 ...

Page 68: ... 68 MEMO ...

Page 69: ...P No 3828A20339A June 2006 Printed in Korea ...

Reviews: