– 25 –
2) Indoor Unit installation
¥L
The mounting floor should be strong and solid
enough to prevent it from vibration.
¥M
Drill the piping hole with 70mm diameter hole-core
drill at either the right or the left of indoor unit. The
hole should be sightly slant to the outdoor side.
¥N
Insert the plastic tube through the hole.
¥O
Cut the extruded outside part of the plastic tube, if
necessary.
3) Outdoor unit Installation
¥L
Install the outdoor unit on the concrete or any solid
base securely and horizontally by securing it with
bolts (Ø12mm) and nuts.
¥M
If there is any vibration transmitted to the building,
mount the rubber underneath the outdoor unit.
4) Refrigerant amount
Before shipment, this air conditioner is filled with the
rated amount of refrigerant including additional
amount required for air-purging, subject to 5m piping
length. (The rated amount of refrigerant is indicated
on the name plate.) But when the piping length
exceeds 5 meters, additional charge is required
according to the following table.
(Unit: g)
Example) In case of 10m long pipe(one-way), the
amount of refrigerant to be replenished is:
(10 – 5)
×
50 = 250g
Wall
Core Drill
Tilt
Cut if necessary
More than 15mm
Wall
Plastic tube
(Bushing)
INSIDE
OUTSIDE
200mm
70mm
70mm
8
9
m
m
REFRIGERANT CHARGE
50g per 1 m
MODEL
5HP
Summary of Contents for LP-E5020CL
Page 12: ... 12 3 LP E5020CL LP E5022CL CA WIRING DIAGRAM ...
Page 13: ... 13 4 LP E5022HL HA ...
Page 66: ... 66 10 ELECTRONIC CONTROL DEVICE 10 1 MAIN P C B ASM ...
Page 68: ... 68 11 1 Circuit and Troubleshooting 11 SCHEMATIC DIAGRAM ...
Page 71: ... 71 6 51 49 47 44 50 14 11 11 1 12 10 10 1 8 9 9 1 9 2 46 42 40 48 5 6 7 49 45 55 43 1 ...