6. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28°C.
• During heating operation, if piping temperatures fall below 26°C fan stops.
• The operation diagram is as following.
7. Defrost Control
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from
starting of heating operation and more than.
• Defrost ends after 10 minutes pass from starting of defrost operation or when the outdoor pipe temperature rises
over 12°C even if before 10 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes pass from
ending of the first defrost and more than.
– 21 –
INDOOR PIPE
TEMP.
INDOOR FAN
SPEED
Selecting
fan speed
OFF
OFF
LOW
1min
Maximum
COMPRESSOR
ON
28
°
C
26
°
C
More than 45 minutes of
heating operation
Outdoor Pipe Temp.
Indoor Fan
Compressor
4-Way Valve
ON
ON
ON
ON
OFF
ON
OFF
HOT-
START
ON
ON
OFF
OFF
ON
12
°
C
(Defrost OFF)
-6
°
C
(Defrost ON)
Within
10minutes
Defrost
Defrost
More than 45 minutes of
heating operation
Less than 5 minutes
Summary of Contents for LP-E5020CL
Page 12: ... 12 3 LP E5020CL LP E5022CL CA WIRING DIAGRAM ...
Page 13: ... 13 4 LP E5022HL HA ...
Page 66: ... 66 10 ELECTRONIC CONTROL DEVICE 10 1 MAIN P C B ASM ...
Page 68: ... 68 11 1 Circuit and Troubleshooting 11 SCHEMATIC DIAGRAM ...
Page 71: ... 71 6 51 49 47 44 50 14 11 11 1 12 10 10 1 8 9 9 1 9 2 46 42 40 48 5 6 7 49 45 55 43 1 ...