(2) Evacuation
(All amount of refrigerant leaked)
• Procedure
1. Confirm that both the liguid side valve and gas
side valve are set to the opened position.
2. Connect the vaccum pump to the center hose of
the manifold gauge.
3. Connect the service port of the gas side valve to
the low side of the gauge.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved
toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the
vacuum pump, and confirm that the gauge nee-
dle does not move(approximately 5 minutes
after turning off the vacuum pump).
6. Disconnect the charge hose from the vacuum
pump.
- Vacuum pump oil.
If the vacuum pump oil becomes dirty or deplet-
ed,replenish as needed.
7. Mount the valve caps and the service port caps.
8. Apply steps from 1 to 7 to each unit (A-unit, B-
unit) by the same method.
- 41 -
Indoor unit
Liquid side
Outdoor unit
Close
2-Way
valve
3-Way
valve
Open
Gas side
manifold gauge
Hi- handle
(CLOSE)
Low- handle
(OPEN)
Vacuum pump
Summary of Contents for LM-3061B2L
Page 1: ...Multi Type Room Air Conditioner SERVICE MANUAL MODEL LM 3061H2L M LM 3061B2L LM 3061C2L M ...
Page 51: ... 51 Electronic Control Device LM 3061C2L M 1 Indoor MAIN P C B ASM LM 3061H2L M LM 3061B2L ...
Page 52: ... 52 2 Outdoor MAIN P C B ASM LM 3061H2L M LM 3061B2L 3 DISPLAY P C B ASM ...
Page 53: ... 53 Schematic Diagram 1 Indoor LM 3061H2L M LM 3061B2L ...
Page 54: ... 54 LM 3061C2L M ...
Page 55: ... 55 2 Outdoor LM 3061H2L M LM 3061B2L ...
Page 62: ... 62 Memo ...
Page 63: ...P No 3828A20023H December 2002 Printed in Korea ...