10. High-Static Motor Connection (For 48K/60K Model)
20
• If working condition of indoor unit is higher than that of
standard static pressure (10mmAq) change the Indoor
Motor wire housing for standard motor housing for higher
external static Pressure (15mmAq).
1. High-Static Motor Connection (For 48K Model)
Control box
Wire Color(YL, BK, BL, OR)
For Higher E.X.P(15mmAq)
Wire Color(BK, BL, RD, OR)
For Standard E.X.P(10mmAq)
Control box
Wire Color(YL, BK, BL, OR)
For Standard E.X.P(10mmAq)
Wire Color(BK, BL, RD, OR)
For Lower E.X.P(6mmAq)
• If working condition of indoor unit is lower than that of
standard static pressure (10mmAq) change the Indoor
Motor wire housing for standard motor housing for lower
external static Pressure (6mmAq).
2. Motor Connection (For 60K Model)