23
Static Pressure(mmAq)
Setting Value
0
2
4
6
8
10
Model Name Step(Hi/Med/Lo)
LB-H1860
**
LB-H2460
**
16.5 CMM
14.5 CMM
13 CMM
18 CMM
16.5 CMM
14 CMM
32 CMM
29 CMM
26.5 CMM
235
245
254
230
240
255
235
247
254
230
238
252
215
235
252
230
245
253
225
235
248
210
230
250
230
245
253
215
230
245
50
210
245
150
235
250
180
215
240
-
-
-
1
230
248
[Table. 1]
[Table. 2]
Note: 1. Be sure to set the value refering table 1. Unexpected set value will cause
mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate
varies.
ENGLISH
LB-G3660
**
LB-G3680
**
Static Pressure(mm Aq)
0
2
4
6
8
10
15
Model Name
Step
CMM
CMM
CMM
CMM
CMM
CMM
CMM
High
48.5
46.5
45
43.5
42
40
40
Med
43
41.5
39.5
38
36.5
35
35
Low
39
37.5
36
34.5
33
31
30
High
58.5
57
55
53
51
49
44
Med
54
52.5
51
49
47
45
39
Low
49
47.5
46
44
42
40
34
High
54
52.5
51
49
47
45
Med
49
47.5
46
44
42
40
Low
44
42.5
41
39
37
35
LB-E6080
**
(Standard)
LB-E4880
**
LB-E6080
**
(Low Static)
1) The above table shows the correlation of External Static Pressure & AIR FLOW.
2) Duct work must be designed within the range of
on installing the unit.
3) Change the wiring diagram referring to page 20 of manual on condition fo High/Low Static
Pressure.
4) If duct work is designed under
External Static Pressure, adjust the External Static
Pressure applying air damper.