52
Multi Type Air Conditioner
Optional Operation - Duct Types
[Table. 1]
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
NOTICE�
• If working condition of indoor unit is higher
than that of standard static pressure
(10mmAq) change the Indoor Motor wire
housing for standard motor housing for higher
external static Pressure (15mmAq).
Control box
Wire Color(YL, BK,
BL, OR) For Higher
E.S.P(15mmAq)
Wire Color(BK, BL,
RD, OR) For Standard
E.S.P(10mmAq)
High-Static Motor Connection (For 48K BE Chassis Model)
Static Pressure(mmAq)
Setting Value
0
2
4
6
8
10
12
14
15
Capacity
Step(Hi/Med/Lo)
16.5 CMM
235
230
225
215
180
18 kBtu/h
14.5 CMM
245
238
235
230
215
BH
13 CMM
254
252
248
245
240
18 CMM
220
205
190
170
1
24 kBtu/h
16.5 CMM
235
230
220
200
100
14 CMM
250
240
235
230
210
26.5 CMM
153
150
150
148
130
1
30 kBtu/h
23 CMM
173
173
175
175
170
155
BG
20 CMM
195
195
193
193
190
190
32 CMM
230
230
225
220
150
1
36 kBtu/h
29 CMM
240
238
237
235
230
220
26.5 CMM
245
245
243
243
240
240
40 CMM
230
225
220
215
205
200
190
180
160
BR
48 kBtu/h
35 CMM
250
245
240
235
230
220
215
210
200
30 CMM
255
255
255
250
245
240
235
230
225
Chassis