Installation Manual
53
Optional Operation - Duct Types
Static Pressure(mm Aq)
0
2
4
6
8
10
15
Model Name
Step
CMM
CMM
CMM
CMM
CMM
CMM
CMM
High
48.5
46.5
45
43.5
42
40
40
Med
43
41.5
39.5
38
36.5
35
35
Low
39
37.5
36
34.5
33
31
30
LMNH/C486BEA0
1) The above table shows the correlation of External Static Pressure & AIR FLOW.
2) Duct work must be designed within the range of
on installing the unit.
3) Change the connection of the indoor fan motor connector to increase the moror speed to dbtain
similar CFM at 15mmAq stastic pressure.
4) If duct work is designed under
External Static Pressure, adjust the External Static Pressure
applying air damper.
R
S
T
N
R S T
N
Outdoor Unit
Power Supply Cable
building
Terminal
block
change
Occurrence of strange noise from
compressor
No variation of pressure gages.
Troubles and Solutions
T
roubles
Solutions
Outdoor unit circuit
Change the R,S wires to the terminal
block.
➲
➲
➲
If the main cable for power supply is connected incorrect or wrong, it shall cause strange noise
from the compressor and cooling operation does not work.
External Static Pressure & Air Flow (For 48K BE Chassis Model)
Checking the Power Cord (For 48K BE Chassis Model)